Class A Chimney/Masonry Chimney Conversion - kozy heat CALLAWAY 40 Installation And Operation Manual

Direct vent gas fireplace
Table of Contents

Advertisement

7.5 Class A Chimney/Masonry
Chimney Conversion
This appliance is approved to be adapted for Class A/Masonry
Chimney conversion with kits utilizing a 4" (102mm) flexible exhaust
by any vent manufacturers listed in Section 7.1 Approved Vent
Systems on page 45.
Before conversion, have the existing installation inspected by a
qualified chimney sweep or professional installer. The existing
chimney system must be in serviceable condition, and functionally
sound. Before proceeding with following installations, check with
local building jurisdiction to verify this type of installation is allowed
in your area.
Follow DIAG. 3 for allowable venting configurations for installation
in existing through-the-ceiling, Class A/Masonry chimney. Route the
exhaust gases and intake air through the existing Class A/Masonry
chimney.
7.5.1 4" Flex Pipe Venting Configurations
IMPORTANT: Horizontal vent sections require at least 1/4" (6mm) rise
for every 12" (305mm) of travel.
IMPORTANT: Care should be taken when installing flexible pipe to avoid
a tight bend that may cause abrasion or damage to the flexible pipe.
The vent option listed below allows for a minimum of 0" (0mm) to a
maximum of 24" (610mm) horizontal run using rigid or flexible pipe.
(i) Minimum / Maximum Vent Vertical Terminations:
45° elbow + 4" x 6-5/8" reducer + Retro Connector + 10' (3.05m)
minimum length of 4" aluminum flexible pipe / 50' (15.24m)
maximum length of 4" aluminum flexible pipe + top adapter +
termination cap
50 VENTING
(A) Header Heat Shield
(B) Stand-off Assembly
(C) 45° Elbow
(D) Reducer
i
A
B
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
DIAG.3 4" FLEX PIPE CHIMNEY CONVERSION
(E) Retro Connector
(F) Top Adapter
(G) Termination Cap
F
D
C
E
#CLW-40 R.3 November 2021
G
50'
(15.24m)
G
10'
(3.05m)