3.7.2.2 Clearances to Sprinkler
In a situation where a sprinkler head is installed within the
proximity of a vented cavity air discharge opening, Figure 3.13
MUST be followed.
The distance between a sprinkler head and discharge opening
cannot be less than 60" (1524mm) in length at every point from
the origin of the discharge opening. You must also verify the
sprinkler head sensor is set to the proper heat setting so it does
not activate when the room heats up from the fireplace being
operated normally.
Please follow local building codes to determine what
temperature setting is relevant for your installation.
Figure 3.13, Clearance from Air Discharge Opening to Sprinkler Head
3.7.2.3 Clearances to Combustibles
Table 3.2, Minimum Appliance Clearances to Combustible Material for Vented Cavity and KZK
From appliance top stand-off brackets
From appliance left and right stand-off brackets
From appliance back stand-off brackets
From appliance corners
From appliance front
Appliance sides to an adjacent sidewall
Mantel 6" (152mm) deep from fireplace finishing edge
Mantel 6" (152mm) deep from fireplace enclosure floor
Minimum height of fireplace enclosure
22 FRAMING
60"
(1524mm)
MIN
Air Discharge Opening
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
Ceiling
VENTED CAVITY INSTALLATIONS
0"
0"
0"
3"
36"
0"
0"
26-5/8"
74"
#CLW-40 R.3 November 2021
0mm
0mm
0mm
76mm
914mm
0mm
0mm
676mm
1880mm