Installation
The GFANN-80 cover must be attached to the annunciator backplate before mounting the annunciator to the electrical box/wall. The
cover cannot be reattached or removed after the annunciator has been mounted.
Annunciator mounted on
surface wedge from the

Wiring GFANN-80 to FACP

The following steps can be used as a guide to wire the annunciator. Make certain all power has been removed from the FACP prior to
annunciator installation.
1.
Route wires from hole in backplate, through wiring channel and then to GFANN-80 terminal block TB1.
2.
Remove appropriate amount of wire insulation.
3.
Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B). Make certain to connect A to A and B
to B.
4.
If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1 terminals 3 & 4. Make certain to connect A to
A and B to B.
5.
Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2 (+). Make certain to observe proper
polarity.
6.
If appropriate, connect the power wiring going to the next device to terminals
1 (-) & 2 (+). Make certain to observe proper polarity.
7.
After all connections are made, remove extra wire from inside of annunciator by dressing it neatly through wire channel, with any
excess wire pushed back through hole into electrical box.
38
ANN-SB80KIT
wiring channel
wires
TB1
Annunciator mounted on
surface backbox from the
ANN-SB80KIT
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
ANN-BUS Devices
Annunciator mounted on
stacked surface wedge
and backbox from the