Fan Control - Regin OPTIGO ARDO Manual

Table of Contents

Advertisement

Summer mode
Table 4-26 Settings for Summer mode
Variable
Date for start of summer period
Month for start of summer period
Date for end of summer period
Month for end of summer period
Outdoor temp for switch between
summer / winter (°C)
Outdoor temp hysteresis for switch
between summer / winter (°C)
4.4.3

Fan control

Ventilation
Fan control
Fans
Supply air fan
Extract air fan
Fan comp. curve
Fans
Table 4-27 Settings for fans
Variable
Offset supply air fan when free
cooling (%)
Offset extract air fan when free
cooling (%)
Supply air fan
Table 4-28 Settings for supply air fan
Variable
Start delay (s)
Stop delay (s)
Outdoor air damper stop delay (s)
SAF speed min limit (%)
SAF speed max limit (%)
Optigo
Ardo
manual, Rev. A
Information for the specialist - Configuration
Read/Write
Default
value
W
1
W
4
W
1
W
10
W
13
W
0,5
Read/Write
Default
value
W
0
W
0
Read/Write
Default
value
W
60
W
180
W
0
W
0
W
100
Min/Max
Note
1/31
1/12
1/31
1/12
0/99
0/99
Min/Max
Note
-100/100
-100/100
Min/Max
Note
0/3600
0/3600
0/3600
0/100
0/100