Free cooling
Read more about free cooling in 3.6 Free cooling.
Table 4-32 Settings for free cooling
Variable
Free cooling mode
Running if day outdoor temperature
> (°C)
Stop if night outdoor temperature >
(°C)
Stop if night outdoor temperature <
(°C)
Stop if room temperature < (°C)
Free cooling start hour (h)
Free cooling stop hour (h)
Time to block heat output after free
cooling (min)
Fan-kick temperature check (s)
Fan-kick interval time (min)
Start when extract - outdoor > (°C)
Support control
Read more about support control in 3.7 Support control.
Table 4-33 Settings for support control
Variable
Support control mode
Min time for support control (min)
Start heating room temperature (°C) W
Stop heating room temperature (°C) W
Setpoint heating (°C)
Start cooling room temperature (°C) W
Stop cooling room temperature (°C) W
Setpoint cooling (°C)
4.4.5

PID controllers

Ventilation
PID controllers
Room air controller
Extract air contr.
Optigo
Ardo
manual, Rev. A
Information for the specialist - Configuration
Read/Write
Default
value
R
W
22
W
18
W
10
W
18
W
0
W
7
W
60
W
180
W
60
W
2
Read/Write
Default
value
R
W
20
15
21
W
30
30
28
W
12
Min/Max
Note
10/40
10/40
10/40
10/40
0/23
1/24
0/600
0/3600
0/600
1/5
Min/Max
Note
0/600
10/40
10/40
-20/150
10/40
10/40
-20/150
51 (76)