Download Print this page
Regin Optigo OP10 Series Manual

Regin Optigo OP10 Series Manual

Pre-programmed, configurable controller for simple applications
Hide thumbs Also See for Optigo OP10 Series:

Advertisement

Quick Links

Language independent
Simple configuration via the backlit display
Input for external setpoint device
Optigo OP10 is a pre-programmed controller that can
be used for control of temperature in air handling and
heating applications. It is a stand-alone controller for
simpler applications. Optigo is extremely easy to install,
commission and control.
Optigo uses a display with an encoder knob, making
its built-in menu system very easy to use. Settings
are entered by turning the encoder knob to a desired
parameter/value. A value is then approved by pressing the
knob.
Models
The Optigo series comprises two different models, OP5U
and OP10.
OP5U has 5 in-/outputs and OP10 has 10 in-/outputs.
OP10 is available in two models:
• OP10 with 24 V AC supply voltage
• OP10-230 with 230 V AC supply voltage
Applications for OP10 and OP10-230
Optigo OP10 is pre-programmed with a choice of five
different control modes:
1. Supply air control
2. Supply air control with outdoor compensation
3. Cascaded room / extract air temperature control
4. Radiator circuit control
5. Domestic hot water control
Optigo OP10
OP10
Pre-programmed, configurable controller for
simple applications
The Optigo OP10 range of controllers controls
temperature. They are intended for DIN-rail mounting.
Pre-loaded with several application modes
24 V or 230 V AC supply voltage
Week-based clock / calendar function
Inputs and outputs
Optigo OP10 has:
• 2 analogue inputs, PT1000
• 1 SPI input for an external setpoint device
• 1 universal input, PT1000 or digital
• 2 digital inputs
• 3 digital outputs
• 2 analogue outputs, 0...10 V DC
Internal clock
Optigo OP10 has a built-in week-based real time clock
with a number of different scheduler alternatives.
Easy to install
Optigo is suitable for DIN-rail or cabinet mounting. Since
the terminals are detachable, all connections can be made
before Optigo is installed.
Optigo has been developed in accordance to our Ready-
Steady-Go concept, simplifying every step from installation to
management.
revision
06 2017

Advertisement

loading

Summary of Contents for Regin Optigo OP10 Series

  • Page 1 revision Optigo OP10 06 2017 OP10 Pre-programmed, configurable controller for simple applications The Optigo OP10 range of controllers controls temperature. They are intended for DIN-rail mounting. • Pre-loaded with several application modes • Language independent • Simple configuration via the backlit display •...
  • Page 2 Optigo OP10 Display and encoder knob Display - Base level This is an example of the display when in Base level view All setting and configuration is performed using the mode. It is normally shown when there is no operator display and encoder knob on the front of the controller.
  • Page 3: Function Overview

    Optigo OP10 Configuration All configuration menus lie in the 10-seconds level. This level is accessed from the Base Display by pressing and holding the encoder button for 10 seconds. There are numerous configuration menus covering all available options and combinations. In some cases, making a certain choice in one menu will mean that you will only see certain other menus.
  • Page 4: Application Examples

    Optigo OP10 Application examples Optigo OP10 can be configured to any one of the following control modes. The three control modes on this page have much in common, and will therefore be treated in a single section. Supply air control Cascade connected room/extract air temperature control The supply air temperature is kept at the setpoint value...
  • Page 5 Optigo OP10 Radiator circuit control with outdoor curve Domestic hot water control The water temperature setpoint is changed according The water temperature is kept constant by controlling the to the outdoor temperature. A single PI control loop is output signal on AO1. A single PID control loop is used. used.
  • Page 6: Technical Data

    Optigo OP10 Technical data Supply voltage OP10: 24 V AC ±15 %, 50...60 Hz OP10-230: 230 V AC +10 %, -15 %, 50...60 Hz Internal consumption 4 VA Ambient temperature 0...50°C Storage temperature -20...70°C Ambient humidity Max. 95 % RH Display Numeric/graphic, backlit Protection class...
  • Page 7: Product Documentation

    Optigo OP10 Wiring OP10-230V OP10 Terminal Designation Function Terminal Designation Function 24 V AC 230 V AConly only Optigo 10-230 Optigo 10 Terminal Designation Function Common Change-over relay 5A Reference for DO1 and DO2 Digital output Digital output AGND Reference for AO1 and AO2. 0...10 V DC output 0...10 V DC output Digital input...

This manual is also suitable for:

Optigo op10Optigo op10-230