2.5.2

Time settings

Optigo
Ardo
has a year-based clock function. This means that a week-schedule with holiday periods for a full
year can be set. The clock has an automatic summertime/wintertime change-over.
It has individual schedules for each weekday plus a separate holiday setting. Up to 24 individual holiday
periods can be configured. A holiday period can be anything from one day up to 365 days. Holiday schedules
take precedence over other schedules.
Each day has up to four individual running periods. There are daily individual schedules for low speed,
normal speed and high speed of the fan, each with up to four running periods.
One output can be used as a timer controlled output, with individual week-schedules with four activation
periods per day. This output can be used to control lighting, door locks etc.
The Time settings menu contains the submenus Time schedule, Holiday schedule and Time/Date.
Time schedule
Holiday schedule
Time/Date
Time settings
Fan low speed
Fan normal speed
Fan high speed
Extra time channel
In the time schedules, four periods are available for each day of the week. Also, four periods are available for
days that are configured as holidays in the holiday schedule. During the periods the assigned circuit is
working with the corresponding setpoint. Outside of a period the system is off.
On
Off
B2
Figure 2-1 Time schedule
The above figure shows an example of period states. It is not possible for periods to overlap each other.
Timer Low speed, Normal speed, High speed
There are sixteen separate settings menus for each timer channel, two for each weekday and two extra for
holidays. Holiday schedules take precedence over other schedules.
14 (76)
Off
E2
B1
On
E1
Off
Begin/End
Optigo