  • Page 2 Our goal is to make real estates in the world more energy efficient. Regin is an international group and our products sells in over 90 countries. Thanks to our global presence with strong local representation, we are well aware of the requirements of the market, as well as of how our products and systems function under the most variable conditions.
  • Page 3: Table Of Contents

    Table of Contents 1 Introduction ..........................5 About EXOcompact ......................5 About this manual.......................5 2 General information........................6 DIN rail mounting inside a cabinet..................6 Maintenance and service ......................6 2.2.1 Changing the battery....................6 2.2.2 Changing the fuse ....................7 2.2.3 Resetting the application memory ................7 Display ..........................8 Installation recommendations....................9 3 EXOcompact Ardo........................10...
  • Page 4 Table of Contents Appendix B Model overview .......................27 EXOcompact Ardo ......................27 EXOcompact Eedo ......................27 EXOcompact Vido ......................27...
  • Page 5: Introduction

    This manual provides descriptions of the EXOcompact Ardo, Eedo and Vido hardware-related information concerning controller connections, wiring, mounting, maintenance and service, and so on. All models are configured and commissioned by using Regin's EXOdesigner software, which is described in depth in EXOhelp.
  • Page 6: General Information

    General information General information 2.1 DIN rail mounting inside a cabinet To mount the controller: 1. Pull out the fastener. 2. Attach the controller to the rail. 3. Push in the fastener to secure the controller. Figure 2-1 Attaching the controller to the DIN rail. 2.2 Maintenance and service W W a a r r n n i i n n g g ! ! Before installation or maintenance, the power supply must first be disconnected in order to prevent potentially lethal electric shocks! Installation or maintenance of this unit should only be carried...
  • Page 7: Changing The Fuse

    General information 2. Remove the top of the casing by pressing the two tabs on each side of the casing, and then lift up the top of the casing carefully. Figure 2-2 Removing the top of the casing. 3. Change the battery. A lithium CR2032 battery is used. 4.
  • Page 8: Display

    General information Figure 2-3 Resetting the application memory. 2.3 Display The display has 4 rows of 20 characters each. It has background illumination. The illumination is normally off, but is activated as soon as a button is pressed. The illumination will be turned off again after a period of inactivity.
  • Page 9: Installation Recommendations

    General information Table 2-1 Summary of the function of the buttons (continued) The buttons Functions Function in Alarm Mode ✓ Enter change mode and erase the value ✓ Closes the menu containing available in the display. alarm manoeuvres without changing the ✓...
  • Page 10: Exocompact Ardo

    EXOcompact Ardo EXOcompact Ardo 3.1 Status indications 3.1.1 XCA203…-4 A LED is located at the top of the controller cassette and provides information about the controller status and behaviour. LED colour Description Green, solid Power on and communication is established Red, solid Battery problem Yellow, blink 2.5 Hz...
  • Page 11: Terminals And Wiring Diagram

    EXOcompact Ardo 3.2 Terminals and wiring diagram 3.2.1 Model XCA203W-4 The controller terminals are shown in Figure 3-1 and described in Table 3-1. 2 G0 10 GDO 11 DO1b 12 DO2b 13 DO3b 14 GDO 15 DO4b 16 DO5b 17 DO6b 20 AGND 21 AI1a 22 AI2a...
  • Page 12 24 AI3a 25 AI4a 31 CI1a Condensation input a Input dedicated for Regin’s condensation detector KG-A/1. 32 CI2a Ethernet communication port 8P8C modular connector used for Ethernet - TCP/IP communication. 40 AO1a Analog output a Output used for e.g.
  • Page 13 EXOcompact Ardo The wiring diagram in Figure 3-2 exemplifies controller connections usage. Ardo G | + 24 V AC G0 | - (COM+) (COM-) 10 GDO DO1b E 70 DO2b DO3b (COM+) (COM-) DO4b DO5b E 60 DO6b EDSP-K3 °C 20 Agnd Room unit AI1a...
  • Page 14: Models Xca

    EXOcompact Ardo 3.2.2 Models XCA…-4 The controller terminals are shown in Figure 3-3 and described in Table 3-2. P1 RxTx P2 RxTx 2 G0 TCP/IP 4 +C B 50 10 GDO A 51 11 DO1b N 52 12 DO2b E 53 B 60 13 DO3b A 61...
  • Page 15 EXOcompact Ardo Table 3-2 XCA…-4 controller terminals descriptions Terminal № and Type Description designator Supply voltage 24 V AC supply voltage. 2 G0 Supply voltage (reference) 24 V AC supply voltage (reference). Ground Earth ground. 4 +C +24 V DC, reference for DI 10 GDO Digital ground Signal ground for digital outputs DO.
  • Page 16 EXOcompact Ardo Figure 3-4 XCA…-4 wiring example, AC installation Figure 3-5 Wiring detail, AC/DC mixed installation EXOcompact Ardo, Eedo and Vido manual, Rev.
  • Page 17: Exocompact Eedo

    EXOcompact Eedo EXOcompact Eedo 4.1 Status indications A LED is located at the top of the controller cassette and provides information about the controller status and behaviour. LED colour Description Green, solid Power is on and all is O. Red, solid Battery problem Yellow, blink 2.5 Hz Identification (wink)
  • Page 18 Input used for e.g. presence, open window, or change-over detection 63 DI2b 65 DI3b 67 CI1a Condensation input a Input dedicated for Regin’s condensation detector KG-A/1 71 AO1a Analog output a Output used for e.g. valve, damper, or EC fan control 73 AO2a...
  • Page 19 EXOcompact Eedo The wiring diagram in Figure 4-2 exemplifies controller terminal usage. 230 V AC Eedo L | + 230 V AC N | - 10 N1 AO4a 0...10 V DO1d AGND AO3a AGND DO2d AO2a N3-5 AGND DO3c AO1a DO4c AGND DO5c...
  • Page 20: Exocompact Vido

    EXOcompact Vido EXOcompact Vido 5.1 Status indications No status indications are available for this model. 5.2 Terminals and wiring diagram 5.2.1 Models XCV193…-2 8x PT1000 0..10V In/Out 0..10V In/Out MBUS* View of terminal base * Depending on the model ext. TCP/IP Display N N o o t t e e ! ! Analogue inputs, digital inputs and universal analogue I/O:s must refer to a signal ground...
  • Page 21 EXOcompact Vido Table 5-1 XCV193…-2 controller terminals descriptions (continued) Terminal № and Type Description designator 11 DO6 Digital output Output terminal DO6 Not used 13 DO7 Digital output Output terminal DO7 Power supply Used for power supply to the digital output DO7 15 L Supply voltage 230 V AC supply voltage...
  • Page 22: Appendix A Technical Data

    Technical data Appendix A Technical data A.1 EXOcompact Ardo A.1.1 General data Supply voltage 24 V ~ (21…27 V ~ 50…60 Hz) / 20…36 V DC (not units with a CI input) Power consumption 4 VA Protection class IP20 Ambient humidity Max.
  • Page 23: Ethernet Port

    Technical data A.1.5 Ethernet port Port type Ethernet Default protocol EXOline-TCP Supported protocols EXOline-TCP / BACnet/IP / Modbus/IP Cable connection RJ45, 10Base-T/100Base-TX auto-negotiation Cable length Max. 100 m Cabling Min. Cat 5 A.1.6 M-Bus port Port type M-Bus Port number Supported protocols Standard M-Bus master Communication speed...
  • Page 24: Inputs & Outputs

    Technical data A.2.2 Inputs & Outputs Please refer to the manual Inputs and outputs specifications for detailed information regarding the inputs and outputs in this model. Digital outputs, total max. Max 2 A continuous load, total max 6.3 A (fuse 6.3 AT 5 x 20 mm) current (fuse) Power output a (POa) 24 V DC, max.
  • Page 25: Inputs & Outputs

    Technical data Ambient humidity Max. 95 % RH, non-condensing Ambient temperature 0…50 °C Storage temperature -20…+70 °C Operating system EXOrealC Battery backup Memory and real-time clock, at least 5 years Mounting DIN-rail, cabinet or wall, or over a device box Number of modules Display Internal or external (accessory)
  • Page 26: M-Bus Port

    Technical data Cable length Max. 100 m Cabling Cat 5 A.3.6 M-Bus port Port type M-Bus Supported protocols M-Bus Mini Master Number of slaves Communication speed 300…2400 baud Cable connection Screw terminal Cable length Max 100 m A.3.7 Material Material, housing Polycarbonate (PC) EXOcompact Ardo, Eedo and Vido manual, Rev.
  • Page 27 Model overview Appendix B Model overview B.1 EXOcompact Ardo Article Ethern- RS485 M-Bus Display AIa Total I/O:s XCA152W-4 XCA152DW-4 XCA203W-4 XCA282W-4 XCA282DW-4 XCA283W-4 XCA283DW-4 XCA283DWM-4 B.2 EXOcompact Eedo Article Ethern- RS485 Display Total I/O:s XCE163W-1 B.3 EXOcompact Vido Article Ethernet...