Temperature Sequences - Regin OPTIGO ARDO Manual

Table of Contents

Advertisement

Information for the specialist
The room temperature is kept at the setpoint value by controlling the output signals for the sequences. Two
PI loops are used.
Settings and configuration for Room cascade control
Table 3-2 Path to configuration and settings for Room cascade
Feature
Configure input
1
Setting of P-band and I-time
Setpoint room temperature
Setpoint adjustment
1. Configured according to config-file, but can be changed.
Extract air cascade
Cascade control of extract air temperature and supply air temperature to achieve a constant, settable room
temperature. The extract air controller output signal (0-100%) generates the supply air controller's setpoint
value between min and max supply setpoint.
The extract air temperature is kept at the setpoint value by controlling the output signals for the sequences.
Two PI loops are used.
Settings and configuration for Extract air cascade control
Table 3-3 Path to configuration and settings for Extract air cascade
Feature
Configure input
1
Setting of P-band and I-time
Setpoint extract air temperature Ventilation ►Actual/Setpoin-
Setpoint adjustment
1. Configured according to config-file, but can be changed.

3.3 Temperature sequences

The supply air controller output is either a heating demand or a cooling demand depending on if the supply
temperature is over or under the setpoint. This demand is then divided into up to 4 sequences A to D. Each
sequence is configured as Heating, Cooling, Exchanger, Damper, or Not used depending on the selected
configuration.
Each sequence has it own PID-settings that can be set in the Ventilation menu in the display.
Each of these output sequences can be bound to either an analog output, to one pulse-width modulated
(PWM) digital output with a settable period time, or to a start/stop digital output.
22 (76)
Menu path in display
Configuration ►Inputs/Output-
s►Analog inputs►Room air
temperature
Ventilation ►PID►Room air
controller
Ventilation ►Actual/Setpoint►-
Room air controller
Ventilation ►Actual/Setpoint►-
Room air controller
Menu path in display
Configuration ►Inputs/Output-
s►Analog inputs►Extract air
temperature
Ventilation ►PID► Extract air
controller
t►Extract air controller
Ventilation ►Actual/Setpoin-
t►Extract air controller
Variable
Setpoint room temperature
Setpoint adjustment
Variable
Setpoint extract air
Setpoint adjustment
Note
Note
Optigo
Ardo
manual, Rev. A