Appendix A Technical Data; Optigo Ardo; General Data; Ethernet Port Data - Regin OPTIGO ARDO Manual

Table of Contents

Advertisement

technical data
Appendix A
A.1 Optigo
Ardo
A.1.1 General data
Supply voltage
Power consumption
Ambient temperature
Ambient humidity
Storage temperature
Protection class
Connection
Memory backup
Display
Mounting
Casing
Dimensions (WxHxD)
Battery type
Battery life
Operating system
A.1.2 Ethernet port data
Port type
Default protocol
Supported protocols
A.1.3 Inputs & outputs
Analog inputs (AI)
Digital inputs (DI)
Universal inputs (UI)
Analog outputs (AO)
Digital outputs (DO)
68 (76)
technical data
24 V AC (21...27 V AC) 50...60 Hz / 20...36 V DC
See Table B-1 Optigo Ardo Models in Appendix B Model overview
0...50 °C
Max. 95 % RH
-20...70 °C
IP20
Disconnectable terminal strips, 4 mm
Built-in long life battery gives long backup time of all settings incl. real time
Backlit LCD, 4 rows of 20 characters
DIN-rail or cabinet
Standard Euronorm (8.5 modules wide)
149 x 121 x 60 mm incl. terminals
CR2032 replaceable Lithium cell
Min. 5 years
EXOrealC
Ethernet
EXOline-TCP
EXOline-TCP
For PT1000 or Ni1000 sensors (accuracy ± 0.4 °C) or 0...10 V DC (accuracy ± 0.15 % of full output
signal). 12 bit resolution in the A/D conversion.
For potential-free contacts
Can be set to act as either analog input or digital input with specifications as above
0...10 V DC, 1 mA, short-circuit protected
Mosfet outputs, 24 V AC or DC, 2 A continuous. Max. 8 A in total.