Log on

Log off

Change password

The controller has four different access levels. The choice of access level determines which menus are shown,
as well as which parameters can be changed in the displayed menus.
Guest level does not require logging on, and only permits changes in running mode and gives read-only
access to a limited number of menus.
Operator level gives the same access as Guest level, and in addition, access to change setpoints.
Service level gives the same access as Operator level, and in addition, access to change controller
settings and manual mode.
Admin level gives full read/write access to all settings and parameters in all menus.
4.9.1
Log on
1. Browse to Access Rights in the main menu and press [►].
Log on
Log off
Change password
2. Select Log on and press [►].
Log on
Enter password:****
Actual level:
None
3. Press [OK] to make a cursor marker appear at the first digit position.
4. Enter the password (4-digit code) by pressing [▲] until the correct digit is displayed. Press the [►] to
move to the next position. Repeat the procedure until all four digits are displayed, and press [OK] to
confirm.
4.9.2
Change password
1. Go to Access Rights in the main menu and press [►].
2. Select Change password and press [►].
Change password for
level:Operator
New password: ****
3. Select Yes and press [OK]
4. Press [OK] to enter change mode.
5. Use the [▲] and [▼] buttons to browse and select the access level to change the password for, and press
[OK] to confirm.
Optigo
Ardo
manual, Rev. A
Information for the specialist - Configuration
61 (76)