C" Group: Intelligent Terminal Functions - Hitachi CP-X200 Instruction Manual

X200 series
Hide thumbs Also See for CP-X200:
Table of Contents

Advertisement

"C" Group: Intelligent Terminal Functions

The five input terminals [1], [2], [3], [4], and [5] can be configured for any of 31 different
functions. The next two tables show how to configure the five terminals. The inputs are
logical, in that they are either OFF or ON. We define these states as OFF=0, and ON=1.
The inverter comes with default options for the five terminals. These settings are
initially unique, each one having its own setting. Note that European and US versions
have different default settings. You can use any option on any terminal, and even use
the same option twice to create a logical OR (though usually not required).
NOTE: Terminal [5] has the ability to be a logical input, and to be an analog input for a
thermistor device when PTC function (option code 19) is assigned to that terminal.
Input Terminal Configuration
Functions and Options – The
twenty eight options to any of the five logic inputs for the X200 inverters. The functions
C001 through C005 configure the terminals [1] through [5] respectively. The "value" of
these particular parameters is not a scalar value, but it is a discrete number that selects
one option from many available
For example, if you set function C001=00, you have assigned option 00 (Forward Run) to
terminal [1]. The option codes and the specifics of how each one works are in
Func.
Name /
Code
SRW Display
C001
Terminal [1] function
IN-TM 1
C201
Terminal [1] function,
2nd motor
2IN-TM 1
C002
Terminal [2] function
IN-TM 2
C202
Terminal [2] function,
2nd motor
2IN-TM 2
C003
Terminal [3] function
IN-TM 3
C203
Terminal [3] function,
2nd motor
2IN-TM 3
C004
Terminal [4] function
IN-TM 4
C204
Terminal [4] function,
2nd motor
2IN-TM 2
C005
Terminal [5] function
IN-TM 5
C205
Terminal [5] function,
2nd motor
IN-TM 5
function codes
options
.
"C" Function
Description
Select input terminal [1] function, 30
options(see next section)
FW
Select input terminal [1] function for
2nd motor, 30 options(see next
FW
section)
Select input terminal [2] function, 30
options(see next section)
RV
Select input terminal [2] function for
2nd motor, 30 options(see next
RV
section)
Select input terminal [3] function, 30
options(see next section)
AT
Select input terminal [3] function for
2nd motor, 30 options(see next
AT
section)
Select input terminal [4] function, 30
options(see next section)
USP
Select input terminal [4] function for
2nd motor, 30 options(see next
USP
section)
Select input terminal [5] function, 30
options(see next section)
2CH
Select input terminal [5] function for
2nd motor, 30 options(see next
2CH
section)
in the following table let you assign one of
Run
Mode
Edit
3 − 49
3 49
Chapter
4.
Defaults
-FE
-FU
Units
(EU)
(USA)
00
00
[FW]
[FW]
01
01
[RV]
[RV]
02
16
[CF1]
[AT]
02
16
[CF1]
[AT]
03
13
[CF2]
[USP]
18
18
[RS]
[RS]