Determining Wire and Fuse Sizes
The maximum motor currents in your application determines the recommended wore
size. The following table gives the wire size in AWG. The "Power Lines" column applies
to the inverter input power, output wires to the motor, the earth ground connection, and
any other components shown in the "Basic System Description" on
Lines" column applies to any wire connecting to the two green connectors just inside the
front cover panel.
Motor Output
Inverter Model
kW
HP
0.2
1/4
X200-002SFEF/NFU
0.4
1/2
X200-004SFEF/NFU
0.55
3/4
X200-005SFEF
0.75
1
X200-007SFEF/NFU
1.1
1 1/2
X200-011SFEF
1.5
2
X200-015SFEF/NFU
2.2
3
X200-022SFEF/NFU
3.7
5
X200-037LFU
5.5
7 1/2
X200-055LFU
7.5
10
X200-075LFU
0.4
1/2
X200-004HFEF/HFU
0.75
1
X200-007HFEF/HFU
1.5
2
X200-015HFEF/HFU
2.2
3
X200-022HFEF/HFU
3.0
4
X200-030HFEF
4.0
5
X200-040HFEF/HFU
5.5
7 1/2
X200-055HFEF/HFU
7.5
10
X200-075HFEF/HFU
Note 1: Field wiring must be made by a UL-Listed and CSA-certified closed-loop
terminal connector sized for the wire gauge involved. Connector must be fixed
by using the crimping tool specified by the connector manufacturer.
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66ft. (20m).
Note 4: Use 18 AWG / 0.75mm
terminals).
Wiring
Power Lines
2
AWG14 / 2.1mm
2
AWG10 / 5.3mm
2
AWG12 / 3.3mm
2
AWG10 / 5.3mm
2
AWG8 / 8.4mm
2
AWG16 / 1.3mm
2
AWG14 / 2.1mm
(60 C only)
2
AWG12 / 3.3mm
(60 C only)
2
wire for the alarm signal wire ([AL0], [AL1], [AL2]
page
2-7. The "Signal
Applicable
equipment
Fuse (UL-rated,
Signal Lines
class J, 600V)
18 to 28 AWG /
2
0.14 to 0.75 mm
shielded wire
(see Note 4)
2 − 19
2 19
10A
10A
10A
15A
15A
20A
30A
30A
40A
50A
3A
6A
10A
15A
20A
25A