Two Stage Acceleration and Deceleration
When terminal [2CH] is turned ON, the
inverter changes the rate of acceleration and
deceleration from the initial settings (F002
and
F003)
to
acceleration/ deceleration values. When the
terminal is turned OFF, the inverter is
returned to the original acceleration and
deceleration time (F002 acceleration time 1,
and F003 deceleration time 1). Use A092
(acceleration time 2) and A0093 (deceleration
time 2) to set the second stage acceleration
and deceleration times.
In the graph shown above, the [2CH] becomes active during the initial acceleration.
This causes the inverter to switch from using acceleration 1 (F002) to acceleration 2
(A092).
Option
Terminal
Code
Symbol
09
2CH
Two-stage Accelera-
tion and Deceleration
Valid for inputs:
C001~C005
Required settings
A092, A093, A094=00
Notes:
Function A094 selects the method for second
stage acceleration. It must be set = 00 to select
the input terminal method in order for the
[2CH] terminal assignment to operate.
use
the
second
Function Name
State
ON
OFF Frequency output uses the initial acceleration 1
set
of
Output
frequency
[2CH]
[FW,RV]
Description
Frequency output uses 2nd-stage acceleration and
deceleration values
and deceleration 1 values
Example (default input configuration shown—see
page
3–49):
2CH
5
4
- FU models
See I/O specs on
page 4–6.
4 − 17
Target
frequency
second
initial
1
0
1
0
3
2
1
L PCS P24
4 17
t