Run Command Source Setting – For parameter A002, the following table provides a
further description of each option, and a reference to other page(s) for more information.
Code
01
Control terminal – The [FW] or [RV] input terminals control
Run/Stop operation
02
Keypad Run key – The Run and Stop keys provide control
03
ModBus network input – The network has a dedicated coil
for Run/Stop command and a coil for FW/RV
A001/A002 Override Sources – The inverter allows some sources to override the setting
for output frequency and Run command in A001 and A002. This provides flexibility for
applications that occasionally need to use a different source, leaving the standard
settings in A001/A002.
The inverter has other control sources that can temporarily override the parameter
A001 setting, forcing a different output frequency source. The following table lists all
frequency source setting methods and their relative priority ("1" is the highest priority).
Priority
A001 Frequency Source Setting Method
1
[CF1] to [CF4] Multi-speed terminals
2
[OPE] Operator Control intelligent input
3
[F-TM] intelligent input
4
[AT] terminal
5
A001 Frequency source setting
The inverter also has other control sources that can temporarily override the parameter
A002 setting, forcing a different Run command source. The following table lists all Run
command setting methods and their relative priority ("1" is the highest priority).
Priority
A002 Run Command Setting Method
1
[OPE] Operator Control intelligent input
2
[F-TM] intelligent input
3
A002 Run command source setting
Run Command Source
3 − 11
3 11
Refer to page(s)...
4-11
2-24
B-19
Refer to page...
4-12
4-29
4-31
4-22
3-10
Refer to page...
4-29
4-31
3-10