3.7 Outdoor Covered Fireplace Installation

A outdoor covered fireplace installation allows a fireplace to be
installed in an outdoor covered area, where the appliance is protected
from direct precipitation.
Follow the instructions and illustrations in this section for installation
procedures.
3.7.1 Safety Screen Barriers
Hussong Mfg. highly recommends to use black painted safety barriers
in outdoor installations. Other screen barriers that incorporate
a plated or patina finish are highly susceptible to oxidation and
discoloration.
SIDE OF
FIREPLACE
BACK OF
FIREPLACE
The overhang (A) must be a minimum of 1/2 or
greater of the roo ine elevation (B) above the base
of the replace.
EXAMPLE: If roo ine (B) is 10' above the base of replace, the overhang (A) must be 5'
or greater. The width of the overhang to EACH side of the replace (C) must be 5' or greater.
Figure 3.6, Outdoor Covered Fireplace Install - 1
16 FRAMING
ROOF OVERHANG
A
B
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
3.7.2 Requirements
The continuous insulated building envelope and weatherproof
membrane are not to be interrupted by fireplace installation. See
Figure 3.7 on the following page.
Fireplace operation is approved from 40°F to 110°F.
All wiring connections shall be in accordance with outdoor
requirements of NECA NFPA 70.
All clearances and requirements in your appliance manual must
be adhered to.
C
FRONT OF
FIREPLACE
The width of the overhang to each side of the
appliance (C) must be a minimum of 1/2 or
greater of the roo ine elevation (B) above the
base of the replace.
C
#SLA-60 R.8 March 2022