6.8 Outdoor Covered Fireplace Installation

An outdoor covered fireplace installation allows a fireplace to be
installed in an outdoor covered area, where the appliance is protected
from direct precipitation.
Follow the instructions and illustrations for installation procedures.
Drawings are for reference only and your fireplace may look different
than shown.
6.8.1 Safety Screen Barriers
Hussong Mfg. highly recommends to use black painted safety barriers
in outdoor installations. Other screen barriers that incorporate
a plated or patina finish are highly susceptible to oxidation and
discoloration.
The overhang (A) must be a minimum of 1/2 or
greater of the roo ine elevation (B) above the base
of the replace.
Figure 6.7, Outdoor Covered Fireplace Installation
20
INSTALLATION
A
B
EXAMPLE: If roo ine (B) is 10 ft above the base of replace, the overhang (A) must be 5 ft
or greater. The width of the overhang to EACH side of the replace (C) must be 5 ft or greater.
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
6.8.2 Requirements
The continuous insulated building envelope and weatherproof
membrane is not to be interrupted by fireplace installation. See
Figure 6.8 on the following page.
Fireplace operation is approved from 40°F to 110°F.
All wiring connections shall be in accordance with outdoor
requirements of NECA NFPA 70.
All clearances and requirements in this manual must be adhered
to.
C
FRONT OF
FIREPLACE
The width of the overhang to each side of the
appliance (C) must be a minimum of 1/2 or
greater of the roo ine elevation (B) above the
base of the replace.
C
#RVT-29-BAK R.3 November 2019