To connect the DTAM Micro terminal to an RS-485 device:
1. Make sure that the power to the DTAM Micro is off.
2. Use the proper cabling to connect the DTAM Micro communications port
to the port of the controller (PLC-5 channel 0 or SLC 5/03 RS-232 port).
Use cable, Catalog No 2707-NC4 for PLC-5 channel 0 RS-422
connection
Use cable, Catalog No. 2707-NC5 for PLC 5 channel 0 RS-232
connection. The 2707-NC5 cable converts the signals from the
RS-485 port to RS-232 levels.
Use cable, Catalog No. 2707-NC1 for SLC 5/03, 5/04 or 5/05 port and
DH-485 network connections
If you need to make your own cable, refer to the connection diagrams
in Appendix B. The maximum recommended cable length is 200 feet
(60.8 meters).
Important: The DH-485 network cable requires proper shielding,
grounding, and termination. Refer to Data Highway / Data Highway Plus
/ Data Highway-485 Cable Installation Manual (Publication No.
1770-6.2.2).
3. The DH-485 connectors are not electrically isolated. If electrical isolation
is required, use Link Couplers (Catalog No. 1747-AIC) shown on the
previous page.
ATTENTION: Electrical isolation using Link Couplers (Catalog
No. 1747-AIC) is required in applications where the distance
!
between the DTAM Micro terminal and the SLC is greater than
6.5 feet (2 meters).
4. Make sure that the communication parameters of the DTAM Micro
terminal match the host device.
5. Apply power and verify that communications are established.
Chapter 7
Communication
Connections and Setup
7–5