Chapter Objectives
Wiring Guidelines
Communication
Connections and Setup
This chapter describes how to connect the DTAM Micro terminal to and
communicate with peripheral devices. It contains the following sections:
Section
Wiring Guidelines
Connecting RS-232 Devices
Connecting RS-485 Devices
Communicating with a Logic Controller
RS-232 Communications with a PLC-5
RS-232 Communications with an SLC 5/03
RS-232 Communications with an SLC or DH485 Network
RS-232 Communications with a MicroLogix 1000
RS-485/DH–485 Communications with a MicroLogix 1000
Here are some recommendations on how to reduce noise on the
communications connections:
Careful wire routing helps reduce or minimize electrical noise.
Route incoming power to the terminal by a separate path from the
communications cables.
Do not run communications wiring and power wiring in the same conduit.
Where communications and power wiring must cross, make their
intersection perpendicular.
Proper grounding helps to limit the effects of noise due to
Electromagnetic Interference (EMI). To avoid problems caused by EMI,
all cables must be shielded and grounded at one end. Grounding is also
an important safety measure in electrical installations.