Delta Electronics AC Motor Drive VFD-EL User Manual page 101

Vfd-el multiple functions / micro type ac motor drive
Table of Contents

Advertisement

Chapter 4 Parameters|
There are three different types of control modes:
04.04
2-wire
0
FWD /STOP
REV / STOP
2-wire
1
FWD/ REV
RUN / STOP
2
3-wire
04.05
Multi-function Input Terminal (MI3)
04.06
Multi-function Input Terminal (MI4)
04.07
Multi-function Input Terminal (MI5)
04.08
Multi-function Input Terminal (MI6)
Settings
Function
0
No Function
4-58
External Terminal
FWD/STOP
REV/STOP
RUN/STOP
FWD/REV
STOP
Description
Any unused terminals should be programmed to 0 to insure they
have no effect on operation.
MI1:("OPEN":STOP)
("CLOSE":FWD)
MI2:("OPEN": STOP)
("CLOSE": REV)
DCM
MI1:("OPEN":STOP)
("CLOSE":RUN)
MI2:("OPEN": FWD)
("CLOSE": REV)
DCM
RUN
MI1 ("CLOSE":RUN)
:
MI3:("OPEN":STOP)
MI2:("OPEN": FWD)
("CLOSE": REV)
REV/FWD
DCM
Revision August 2008, 2ELE, V1.02
VFD-EL
VFD-EL
VFD-EL
Factory Setting: 1
Factory Setting: 2
Factory Setting: 3
Factory Setting: 4