for(j=0;j<8;j++){
if(reg_crc & 0x01){ /* LSB(b0)=1 */
reg_crc=(reg_crc>>1) ^ 0xA001;
}else{
reg_crc=reg_crc >>1;
}
}
}
return reg_crc;
}
3.5 Address list
The contents of available addresses are shown as below:
Content
AC drive
Parameters
Command
Write only
Revision August 2008, 2ELE, V1.02
Address
GG means parameter group, nn means parameter number,
for example, the address of Pr 04.01 is 0401H. Refer to
chapter 5 for the function of each parameter. When reading
GGnnH
parameter by command code 03H, only one parameter can
be read at one time.
Bit 0-1
Bit 2-3
2000H
Bit 4-5
Bit 6-7
Bit 8-15
2001H
Frequency command
Bit 0
2002H
Bit 1
Bit 2-15
Chapter 4 Parameters|
Function
00B: No function
01B: Stop
10B: Run
11B: Jog + Run
Reserved
00B: No function
01B: FWD
10B: REV
11B: Change direction
00B: Comm. forced 1st accel/decel
01B: Comm. forced 2nd accel/decel
Reserved
1: EF (external fault) on
1: Reset
Reserved
4-93