Multi-Function Output Relay (Ra1, Rb1, Rc1) - Delta Electronics AC Motor Drive VFD-EL User Manual

Vfd-el multiple functions / micro type ac motor drive
Table of Contents

Advertisement

Group 3: Output Function Parameters
03.00

Multi-function Output Relay (RA1, RB1, RC1)

Settings
Function
No Function
0
1
AC Drive Operational
Master Frequency
2
Attained
3
Zero Speed
4
Over-Torque Detection
Baseblock (B.B.)
5
Indication
6
Low-Voltage Indication
Operation Mode
7
Indication
8
Fault Indication
Desired Frequency
9
Attained
Terminal Count Value
10
Attained
Preliminary Count Value
11
Attained
Over Voltage Stall
12
supervision
Over Current Stall
13
supervision
Revision August 2008, 2ELE, V1.02
Active when the drive is ready or RUN command is "ON".
Active when the AC motor drive reaches the output
frequency setting.
Active when Command Frequency is lower than the
Minimum Output Frequency.
Active as long as over-torque is detected. (Refer to Pr.06.03
~ Pr.06.05)
Active when the output of the AC motor drive is shut off
during baseblock. Base block can be forced by Multi-function
input (setting 09).
Active when low voltage(Lv) is detected.
Active when operation command is controlled by external
terminal.
Active when a fault occurs (oc, ov, oH1, oL, oL1, EF, cF3,
HPF, ocA, ocd, ocn, GFF).
Active when the desired frequency (Pr.03.02) is attained.
Active when the counter reaches Terminal Count Value.
Active when the counter reaches Preliminary Count Value.
Active when the Over Voltage Stall function operating
Active when the Over Current Stall function operating
Chapter 4 Parameters|
Factory Setting: 8
Description
4-47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents