Chapter 4 Parameters|
00.10
Reserved
00.11
Reserved
00.12

50Hz Base Voltage Selection

Settings
This parameter determines the base voltage for 50Hz.
00.13

User-defined Value 1 (correspond to max. frequency)

Settings
This parameter corresponds to max. frequency.
When Pr.00-13 is not set to 0, "F" will disappear in frequency mode and the right-most digit will
blink. Many ranges will be changed to Pr.00.13, including potentiometer, UP/DOWN key, AVI,
ACI, multi-step, JOG function and PID function.
When Pr.00.13 is not set to 0 and the frequency source is from communication, please use
Pr.02-18 to change frequency setting because it can't be set at address 2001H.
00.14
Position of Decimal Point of User-defined Value 1
Settings
It is used to set the position of decimal point of Pr.00.13.
Example: when you want to set 10.0, you need to set Pr.00.13 to 100 and Pr.00.14 to 1.
4-30
0
230V/400V
1
220V/380V
0 to 9999
0 to 3
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0
Revision August 2008, 2ELE, V1.02
Unit: 1
Unit: 1