Chapter 4 Parameters|
These parameters determine the increase/decrease of the master frequency when operated
via the Multi-function Inputs when Pr.04.05~Pr.04.08 are set to 10 (Up command) or 11 (Down
command).
When Pr.02.07 is set to 0: increase/decrease the frequency by using UP/DOWN key. It is valid
only when the AC motor drive is running.
When Pr.02.07 is set to 1: increase/decrease the frequency by acceleration/deceleration
settings. It is valid only when the AC motor drive is running.
When Pr.02.07 is set to 2: increase/decrease the frequency by Pr.02.08.
When Pr.02.07 is set to 3: increase/decrease the frequency by Pr.02.08 (unit: pulse input).
02.11

Keypad Frequency Command

Settings
This parameter can be used to set frequency command or read keypad frequency command.
02.12

Communication Frequency Command

Settings
This parameter can be used to set frequency command or read communication frequency
command.
The Selections for Saving Keypad or Communication Frequency
02.13
Command
Settings
This parameter is used to save keypad or RS-485 frequency command.
02.14
Initial Frequency Selection (for keypad & RS485)
Settings
02.15
Initial Frequency Setpoint (for keypad & RS485)
Settings
4-44
0.00 to 600.0Hz
0.00 to 600.0Hz
0
Save Keypad & Communication Frequency
1
Save Keypad Frequency only
2
Save Communication Frequency only
0
By Current Freq Command
1
By Zero Freq Command
2
By Frequency Display at Stop
0.00 ~ 600.0Hz
Unit: 0.01
Factory Setting: 60.00
Unit: 0.01
Factory Setting: 60.00
Factory Setting: 0
Factory Setting: 0
Unit: 0.01
Factory Setting: 60.00
Revision August 2008, 2ELE, V1.02