Ex p Control unit
SILAS
pz

Input of parameters

LED Indicators

Rev. 0
Changing parameters in the Web interface must be carried out in a certain
sequence:
Procedure for changing parameters:
 Activate the parameter setting switch.
 Logging in to the web interface
If you are already logged in, the web interface requires a new log-in.
 Select desired parameter
e.g. po - operating pressure 2.5 mbar (250 Pa)
 Enter parameters
Enter value 250
 Press the "Enter" key to confirm.
 The following window opens. This is to confirm and check the changed
parameter value.
LED
Color
p1
Green
p2
Yellow
p3
Green
p4
Red
Operate
Green
Status
Green
A1-37S2-7D0001_pz_Manual_Exp-Control-Unit_20210923_0_en.docx
Function
Minimum pressure
 Lights up when the minimum pressure is
exceeded
Pre alarm
 Lights up when the value falls below the set
value
Purge pressure
 Lights up during rinse phase and exceeds set
point value
Maximum pressure
 Lights up when the maximum pressure is
exceeded p4 or p5
Release / purge process
 Flashing during purge and on release after
flushing lit
Power Supply / Bypass
 Lights up when supply voltage is applied and
flashes when bypass is activated
Operation