Reading Container Data - Bartec SILASPZ Manual

Ex p control unit
Table of Contents

Advertisement

Operation

Reading container data

Page 64 of 88
Data is retrieved for the control room via a web browser or using an appropriate
software tool to be provided by the customer that is able to send an HTML GET
message equivalent to a browser request across the network to the SILAS
device.
The data format returned from the device is JSON
(see https://de.wikipedia.org/wiki/JavaScript_Object_Notation)
Request:
Reply from the control unit:
Code table:
Key/ID
Parameter
_0x0401
Operating pressure po (setpoint)
_0x0101
Operating pressure po (actual)
_0x0402
Minimum pressure (shutdown pressure level)
_0x0403
Pre-alarm (switching value)
_0x1001
Purge pressure p3 (setpoint)
_0x0201
Purge pressure p3 (actual)
_0x0501
Maximum pressure, operation p4 (switching value)
_0x0502
Maximum pressure, purge p5 (switching value)
_0x1312
Pressure sensor A pa (actual)
_0x132A
Pressure sensor B pb (actual)
_0x0602
Purge time
A1-37S2-7D0001_pz_Manual_Exp-Control-Unit_20210923_0_en.docx
Data for the control room can be
retrieved using the URL:
http://<ip-addr>/info_operator.json
e.g. http://192.169.1.101/info_operator.json
The username and password must be
entered.
Login: "operator"
Password: "operator"
Ex p Control unit
SILAS
pz
Unit
Pa
Pa
Pa
Pa
Pa
Pa
Pa
Pa
Pa
Pa
Seconds
Rev. 0