Commissioning; General; Sequence For The Settings; Parameterization Of Purge Gas Valve - Bartec SILASPZ Manual

Ex p control unit
Table of Contents

Advertisement

Ex p Control unit
SILAS
pz

8 Commissioning

General

Sequence for the settings

Parameterization of purge gas valve

Rev. 0
The following sections describe the initial commissioning of the Ex p control unit.
This means that it is described in detail how the Ex p control unit is set to the Ex
p equipment created.
COMMISSIONING
The operating instructions for the Ex p equipment must be
used for commissioning a set and certified Ex p equipment.
The following procedure is recommended when setting the function parameters:
Start
Ex p settings
Options
Functional test
Settings backup
*
= Setting is to be performed in case of automatic flushing
For the Ex p control unit, purging gas valves are available in the "Proportional" or
"Digital" version. The difference between the two purging gas valve types is the
mode of operation:
Digital purging gas valve = on/off valve. Leakage air compensation takes place
via the setting of the manually adjustable leakage air needle.
Proportional valve = regulating valve. During the purging phase, the internal
pressure is regulated to 87.5% of p5 and during the operating phase to po.
A1-37S2-7D0001_pz_Manual_Exp-Control-Unit_20210923_0_en.docx
Valves
Ex p parameters
Pressure parameter
Characteristics
Enclosure parameter
Settings
Temp.-Sensors
Parameter
Commissioning
Purge mode
*
*
Extended
Network
Language
Page 65 of 88

Advertisement

Table of Contents
loading

Table of Contents