7.5 Entering parameters

7.6 LED displays

Page 50 of 96
Changing parameters in the web interface must be carried out in a certain order:
Procedure for changing parameters:
 Activate parameter switch.
 Log into the web interface.
If you are already logged in, the web interface requires you to log in again.
 Select the desired parameter.
e.g. po - operating pressure 2.5 mbar (250 Pa)
 Enter parameter.
Enter the value 250
 Confirm with the "Enter" key.
 The following window opens. This is to confirm and check the changed
parameter value.
LED
Colour
p1
Green
p2
Yellow
p3
Green
p4
Red
Operate
Green
Status
Green
01-37A2-7D0003_Operating instructions_MPC_20210923_0_en.docx
Function
Minimum pressure
 Lights up when the minimum pressure is
exceeded
Pre-alarm
 Lights up when the pressure falls below the
set value
Flushing pressure
 Lights up during the purging phase and when
the set point is exceeded
Maximum pressure
 Lights up when maximum pressure p4 or p5 is
exceeded
Release / Purging
 Flashes during purging and lights up after
purging when enabled
Supply / Bypass
 Lights up when supply voltage is applied and
flashes when bypass is activated
Ex p control unit
Motor Purge Controller
Rev. 0