Error Messages - Bartec SILASPZ Manual

Ex p control unit
Table of Contents

Advertisement

Ex p Control unit
SILAS
pz

Error messages

Positive messages
Warning messages
Rev. 0
The control units give plain text messages which are divided into 3 categories.
 Positive messages are notifications that do not affect system availability.
 Warning messages are notifications that affect parts of the system.
 Alarm messages are notifications that lead to the shutdown of the
protected device.
Status
Code
00000001
The control unit has started the purging process.
00000002
The control unit has successfully completed the purging process. The main switch or
bridge HS_IN / HS_OUT is not closed.
00000003
The control unit has successfully completed the purging process. The main switch or
bridge HS_IN / HS_OUT is closed and enabled.
00000004
The set point value "p3" purging flow is reached and the purging time counts down.
Status
Code
00000005
The bypass is activated on the control unit.
00000006
The main switch or bridge HS_IN / HS_OUT is not closed.
00000007
The set point value p2 "pre-alarm" is not reached.
00000008
The set point value p4 "Maximum pressure – operation" is exceeded.
00000009
The set point value p5 "Maximum pressure – Purging" is exceeded.
0000000A
The set point temperature value at sensor 1 is exceeded.
0000000B
The set point temperature value at sensor 2 is exceeded.
0000000C
The set point temperature value at sensor 3 is exceeded.
A1-37S2-7D0001_pz_Manual_Exp-Control-Unit_20210923_0_en.docx
Plain text
Purging cycle active
Ex p ready
Ex p enabled
p3 reached
Plain text
Bypass active
Door contact / main switch open
p2 not reached
p4 exceeded
p5 exceeded
Temperature sensor 1 exceeded
Temperature sensor 2 exceeded
Temperature sensor 3 exceeded
Maintenance and care
Page 81 of 88