Vega MINITRAC 31 Operating Instructions Manual page 67

Radiometric sensor for density measurement
Table of Contents

Advertisement

Failure
Code
Text message
F008
Error multi sensor commu-
nication
F013
Sensor signals a fault
F016
Adjustment data exchanged
F017
Adjustment span too small
F025
Invalid linearization table
F030
Process value out of limits
F034
EPROM hardware error
F035
EPROM data error
F036
Faulty program memory
F037
RAM hardware error
F038
Secondary signals failure
F040
Hardware error
F041
Photomultiplier error
F052
Faulty configuration
MINITRAC 31 • Foundation Fieldbus
This status message is inactive by default.
Cause
Additional sensors not switched on
EMC influences
No other sensor available
Error on the current input/digital input
No valid measured value
Connected instruments without function
Values of the min. and max. adjustment
exchanged
The values of the min. and max. adjust-
ment are too close together
Wrong or empty linearization table
(1074, 1075, 1080, 1100, 1106)
Wrong value in the linearization table
(1143, 1144)
Process values are not within the adjust-
ed measuring range
Electronics defective
Error in the internal instrument commu-
nication
Error during software update
Error in RAM
Connection cable to the Secondary in-
strument interrupted
Instrument not defined as Secondary in-
strument
One of the Secondary instruments sig-
nals a failure
Instrument defective (1092, 1126)
Temperature outside the specification
(1091)
Error in the measured value recording
Invalid parameter adjustment
9 Diagnostics and servicing
Rectification
Check wiring between the sensors
Connect the sensors correctly and make
them ready for operation
Check current input
Check connected instruments (Second-
ary instrument)
Correct adjustment data
Correct adjustment data
Create linearization table
Correct linearization table
Repeat adjustment
Restart instrument
Exchanging the electronics
Carry out a reset
Exchanging the electronics
Repeat software update
Exchanging the electronics
Restart instrument
Exchanging the electronics
Check the connection cable to the Sec-
ondary instrument
Define instrument as Secondary
Check Secondary instruments
Restart instrument
Exchanging the electronics
Cool the instrument or protect it with iso-
lation material against heat/cold
Restart instrument
Exchanging the electronics
Carry out a reset