Reset
Menu
Setup
MINITRAC 31 • Foundation Fieldbus
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language, SIL and HART mode.
The following reset functions are available:
Basic settings: Resetting of the parameter adjustments to default
values at the time of shipment. Order-specific settings are deleted.
Default settings: Resetting of the parameter adjustment like under
" Basic settings". In addition, special parameters are reset to default
values. Order-specific settings are deleted.
Peak values of measured value: Resetting of the parameter adjust-
ments in the menu item " Setup" to the default values of the respec-
tive instrument. Order-specific settings remain but are not taken over
into the current parameters.
Peak values of temperature: Resetting of the measured min. and
max. temperatures to the actual measured value.
The following table shows the default values of the instrument. The
values apply for the application " Density". First of all you have to
select the application.
Depending on the instrument version, not all menu items may be
available or they may be differently assigned:
Menu item
Measurement loop name
Isotope
Application
Background radiation
Process value unit
Temperature unit
Adjustment min. process value
Adjustment max. process value
Inner diameter
Linearisation
Damping
Real value correction
Reference value - Relay
Lock adjustment
6 Set up with the display and adjustment module
Default value
Sensor
Cs-137
Density
0 ct/s
g/cm
3
° C
0.500 g/cm
3
1.500 g/cm
3
0.20 m
90000 ct/s and 0.500 g/cm
60 s
0
None
Released
3
47