Procedure
Isotope
Application
MINITRAC 31 • Foundation Fieldbus
Display: Settings, for example language, measured value display
Diagnosis: Information, for example, of device status, peak value,
simulation
Additional adjustments: Instrument unit, reset, date/time, copying
function
Info: Instrument name, hardware and software version, date of manu-
facture, instrument features
Check if the correct language is already set for the display. If not,
you can change the language in the menu item " Display - Menu
language".
Start with the setup of MINITRAC 31.
In the main menu item " Setup", the individual submenu items should
be selected one after the other and provided with the correct param-
eters to ensure optimum setting of the measurement. The procedure
is described in the following.
Stick with the normal sequence of the menu items as closely as pos-
sible.
6.6.1 Setup
In this menu item you can adjust the MINITRAC 31 to the isotope
installed in the source container.
For this purpose, check which isotope is in the source container. You
can find this information on the type label of the source container.
With this selection, the sensitivity of the sensor is adapted in an opti-
mum way to the isotope.
The MINITRAC 31 requires this information for the decay compensa-
tion. An annual recalibration is hence not necessary.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Enter here, the respective application.
This menu item enables adaptation of the sensor to the requested ap-
plication. You can choose between the following applications: " Level",
" Density", " Limit level", " X-ray alarm" or " Real value correction".
6 Set up with the display and adjustment module
59