Vega MINITRAC 31 Operating Instructions Manual page 38

Radiometric sensor for density measurement
Table of Contents

Advertisement

6 Set up with the display and adjustment module
Application
Background radiation
Units
38
Through this selection, the sensitivity of the sensor is adapted per-
fectly to the isotope. The normal reduction of source activity through
radioactive decay is thus taken into account.
The MINITRAC 31 requires this information for the automatic decay
compensation. This ensures error-free measurement over the entire
lifetime of the gamma emitter - an annual recalibration is not neces-
sary.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Enter here, the respective application.
This menu item enables adaptation of the sensor to the requested ap-
plication. You can choose between the following applications: " Level",
" Density", " Limit level", " X-ray alarm" or " Real value correction".
The natural radiation on earth influences the accuracy of the meas-
urement.
With this menu item the natural background radiation can be faded
out.
Note:
Make sure that some products have a self-radiation. This is for ex-
ample the case with oil or potash salt lye. Therefore the tube must be
filled to determine the background radiation.
For this purpose, the MINITRAC 31 measures the natural background
radiation and sets the pulse rate to zero.
In the future, the pulse rate from this background radiation will be
automatically deducted from the total pulse rate. This means: only
the component of the pulse rate originating from the source will be
displayed.
The source container must be closed for this setting (OFF).
In this menu item you can select the units of the process value and
the temperature.
MINITRAC 31 • Foundation Fieldbus