You will want to start programming the drive from scratch. Performing an
"initialization" will reset all parameters back to the factory default. With power off,
simultaneously hold down the "status, main menu & OK" keys. Apply power and
continue to hold the buttons for at least 5 seconds after you apply power to the
drive. If you were successful, the display will read "Drive initialized [A80].
parameter 14-22 to "initialize" and cycling power is an alternative method)
After initializing the drive, the first change to be made is parameter # 0-03.
Changing this parameter to "North America" will set any regional parameters to
North American defaults.
Press the "Quick Menus" key, scroll down to Q2 with the arrow and press the
"OK" to enter the "Quick Setup" menu.
177R0521-VLT_Aqua_Drive_Training_Handout_BODY.indd 17

Mechanical Setup

Plug in the demo drives power cord into a 120 volt outlet
Connect the motor to the drive. Drive terminals 96, 97 & 98 are
used for the motor connections. Also connect the motor ground
wire to the drive chassis.
Place a jumper wire between control card terminals 12 & 27.

Software Setup

17
(setting
4/29/15 2:47 PM