Configuring A Fan - Halton Safe Management 2.0 Installation, Commissioning, Operating, And Maintenance Manual

Table of Contents

Advertisement

Halton Safe Management 2.0 (SM2) - Installation, commissioning, operating, and maintenance guide
Value
Smoke detector
Normally open
Normally closed
If you get errors when doing the task, see Troubleshooting.

5.3.7 Configuring a fan

You can configure 1-3 fans for a Halton Safe Management 2.0 controller. By default, a fan is configured to stop in
the following situations:
▪ An alarm group is being tested.
▪ A smoke detector sends an alarm indication.
▪ There are fire dampers that are not open.
If you want to change the configuration of a fan, do the following:
1. Log in as Installer. For instructions, see
2. Select the fan icon.
The main view of the fan opens.
1.0
Description
Smoke detector
An alarm device with a normally open (NO)
connector
An alarm device with a normally closed (NC)
connector
Logging in as
Installer.