Installation Requirements; Checks Before Installation; Step By Step Instructions; Installing The Halton Safe Management 2.0 Controller - Halton Safe Management 2.0 Installation, Commissioning, Operating, And Maintenance Manual

Table of Contents

Advertisement

Halton Safe Management 2.0 (SM2) - Installation, commissioning, operating, and maintenance guide
Note: Before connecting the system to power, you need to set the addresses of the Halton Safe HSL link units. For
instructions, see
Setting the address of a Halton Safe HSL link

4.1.3 Installation requirements

General
The operating voltage of the Halton Safe Management 2.0 controller is 230 V AC.
Note: It is recommended that an uninterruptible power supply (UPS) is used with the Halton Safe Management 2.0
controller.
Space requirements
Install the Halton Safe Management 2.0 controller in a place that is easily reachable.
The controller is usually installed to the wall. Reserve enough space around the controller for service.
Wiring
Note: The wiring must only be carried out by qualified personnel following the local regulations.
Cabling requirements
▪ The Halton Safe Management 2.0 controller includes a 230 V power plug. The plug type is Schuko CEE7/4,
type F.
▪ Communication cable from the Halton Safe Management 2.0 controller to Halton Safe HSL units:
shielded twisted-pair cables, size 0.5 mm
Depending on external circumstances, the maximum length can be shorter.
▪ Instrumentation cable from Halton Safe HSL units to smoke detectors and fire damper actuators:
shielded twisted-pair cables, size 0.5 mm
▪ Power supply cable from a Halton Safe HSP unit to Halton Safe HSL units: size 3 x 2.5 mm
Note: When designing cabling, take into account the voltage drop of cables.

4.1.4 Checks before installation

Depending on the component you are installing, make sure you have all the needed materials:
▪ Correct type of cabling. For more information, see
▪ Instructions (this document, project-specific wiring diagrams, design drawings)
Note: Cabling is not included in the delivery.

4.2 Step by step instructions

4.2.1 Installing the Halton Safe Management 2.0 controller

1. From the design drawings, determine the installation place.
2. Install the unit securely.
1.0
unit.
2
. For example, 2 x 2 x 0.5+0.5. The maximum length is 1000 m.
2
. For example, 4 x 2 x 0.5+0.5.
Installation
requirements.
All rights reserved ©Halton
17
2
.