18.7 To remove the burner assembly and tray.

1. Complete section 19.1 - 19.6
2. Isolate the gas supply at the inlet isolating 'T' connector.
3. Support the inlet 'T' connector to avoid straining the
pipework and disconnect the appliance from the inlet 'T'
connector.
4. Unscrew the burner tray from the convection box by
removing two locating screws.
5. Slide the burner tray unit clear of the convector box.
6. Replace in the reverse order.
18.8 To access & remove the Inspection panel.
1.Complete sections 19.1 - 19.7
2. Unscrew the 4 screws, then remove and place the
screws and panel to one side carefully.
3. Any inspection or cleaning of debris necessary can now
be carried out.
3. Replace in reverse order, a flue flow test should be
carried out at this stage. Refer to the relevant section of
BS5440 Part 1 for this procedure.
18.9 Checking the aeration setting of the burner.
1. The aeration shutter is factory set. It is important to ensure that the aeration
setting(s) are correct
2. The 600RC/FS, 800RC/FS & 1000RC/FS models burners all use the aeration
setting open at 4.5mm accross the bottom 2 holes.
3. If the setting is not as shown, adjust the aeration setting(s). To do this loosen the
two aeration shutter screws, slide the aeration shutter to the desired position and
tighten the screws.
©
GDC Group Ltd. NOV 2017
INSTALLER GUIDE
Setting for both Front and
Rear Burners on 600 & 800
RC & FS models
Page 40
SCALE 0.500
Setting for both Front and
Rear Burners on 1000 RC &
FS models
4.5 mm