Lumina 750
6.15
Function key 14: Warm up pasteurization
14
à
Start diff.
Test air inlet
For circulation table, Circulation control (page 6).
6.16
Function key 15: Pasteurization
15
à
Max. compost
For circulation table, Circulation control (page 6).
6.17
Function key 16: Cool down conditioning
16
à Extra
Test air inlet
For circulation table, Circulation control (page 6).
6.18
Function key 17: Conditioning
17
Warm up past. 1/2
Extra
à
Setting of how many degrees the air inlet temperature control value must be
lower than the control value compost/tunnel at the beginning of the warm up
pasteurization phase.
Setting of the air temperature check. Before the Lumina 750 automatically switches
to the next phase, the computer will automatically check the air temperature. When
setting is NO, it only checks the temperature of the tunnel. If setting is YES, it also
checks the air inlet temperature.
Extra
Setting of the maximum compost temperature which will be accepted by the Lumina
750. As soon as the compost has reached this temperature, the Lumina 750 must
switch to the next phase (Cool down conditioning) on condition that the minimum
phase time has elapsed. In this case the Lumina 750 will not wait until the maximum
phase time has elapsed.
Setting of the air temperature check. Before the Lumina 750 automatically switches
to the next phase, the computer will automatically check the air temperature. When
setting is NO, it only checks the temperature of the tunnel. If setting is YES, it also
checks the air inlet temperature.