Lumina 750
6.13
Function key 12: Alarm settings
12
Compst alarm
Alarm inlet alarm
O2 alarm
Tunnel<Compost
Min. air inlet
Froststat
All alarm settings are entered at this function key. Refer to chapter Alarm for
information concerning the readout and deactivation of alarms.
If a setting is set to 0, the computer will not give an alarm for this
climate parameter.
An alarm can only activate after the measured value has been
within the alarm limits once.
Setting of the value by which the average compost/tunnel temperature may differ
from the compost control value.
Setting of the value by which the measured air inlet temperature may differ from the
air inlet temperature control value.
Setting of the value the measured O
value.
Setting of the value by which the measured tunnel temperature may be lower than
the average compost temperature.
Setting of the minimum air inlet temperature. If the measured air inlet temperature
drops below this
Minimum air
given.
Setting if a frost thermostat is used (YES). The control computer will give a loud
alarm as soon as this thermostat is activated. External frost security can also be
connected. The fan will be deactivated during this alarm.
The frost thermostat must also interrupt the control signal to the fan.
content may be lower than the O
2
inlet, the fan will be deactivated and a loud alarm
Classic screens
control
2
50