Setting With The Engineering Tool - Toshiba nv Series Instruction Manual

Hide thumbs Also See for nv Series:
Table of Contents

Advertisement

3.3

Setting with the Engineering Tool

Settings to the FL911 module can be done with the engineering tool.
For the operation method of the engineering tool, refer to "Unified Controller nv
series/Integrated Controller V series Engineering Tool 4(Basic) Instruction
Manual"(6F8C1290).
Connect the engineering tool and nv series controller via Ethernet.
The Ethernet connection in the nv controller can be made using the FL911
module. (Figure 3-1 System configuration of the setting example).
Engineering
Tool (PC)
IP Address: 192.168.250.2
Subnet mask: 255.255.255.0
Figure 3-1 System configuration of the setting example
Set the IP address shown in Figure 3-1 to the FL911 module. Using the rotary
switch of the FL911 module, set the lowermost digit of the IP address in
hexadecimal (in this case, convert "2" into hexadecimal and set "0x02," i.e. H=0,
L=2).
Set all the MODE switches of the FL911 module to OFF.
Note
 The switch setting becomes effective from the next startup. After setting, turn ON the power of
the FL911, which is supplied to SA9**, from OFF.
IP Address: 172.16.64.1
Subnet mask: 255.255.192.0
IP Address: 172.16.64.18
P
E
Subnet mask: 255.255.192.0
U
N
8
8
TC-net I/O loop
S
F
A
L
9
9
Unified Controller nv series FL-net (FL911) Module Instruction Manual

3.3 Setting with the Engineering Tool

Ethernet
FL-net
FL-net
product
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fl911

Table of Contents