Figure C-9: F10 - Input Line Supervision - Eaton 9000X User Manual

Af drives
Table of Contents

Advertisement

June 2009
F10 — Input Line Supervision
MN04001004E
F10
Measure mains voltage at input terminals
Mains
OK ?
Yes
Check rectifier-circuit and
dc-capacitors according to instructions
in service manual
Measurements
OK ?
No
Replace defective parts as
recommended in spare part lists
Figure C-9: F10 — Input Line Supervision
For more information visit: www.eaton.com
No
Make corrections to mains, change fuses
If fuses blown, check for possible
internal failures in converter
Occasionally existing line dips or
Yes
disturbances may activate line supervision
function. Ensure quality of line power.
Clear fault memory