Pressure Control Configuration - VAT 615 Series Installation, Operating, & Maintenance Instructions

Butterfly control & isolation valve with extended control range with rs232 interface
Table of Contents

Advertisement

3.6.4 Pressure control configuration

('Control View' or 'Control Performance Analyzer')
1.
Open CV or CPA
2.
Go to «Tools» > «Terminal» and send setup command s:02 according
to application needs. (possibility of adjustment see below)
Command
s:02abcdefgh
configuring Control mode a
Set
s:02a
switch to Control mode a without
configuring
i:02
get configuration actual Control
mode
Get
i:02a
get configuration Control mode a
This command selects control mode, gain factor, sensor response time,
setpoint ramp time, p-gain, i-gain and pump down for the PID controller.
data length 8 characters
a
Control algorithm:
0 = adaptive downstream (default)
1 = fixed PI downstream control
2 = fixed PI upstream control
3 = soft pump
Note: For adjustment of Control algorithm see table below.
a (control mode)
0
adaptive
downstream
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
Installation, Operating & Maintenance Instructions
Series 615 DN 40 (I.D. 1.5"), RS232
Local
operation:
(within 10ms after reception of
Describtion
s:02
s:02
i:02abcdefgh
i:02abcdefgh
parameter description
b Gain Factor: (default is 8 = 1.00)
0 = 0.10, 1 = 0.13, 2 = 0.18, 3 = 0.23, 4 = 0.32, 5 = 0.42, 6 = 0.56, 7 = 0.75, 8 = 1.00,
9 = 1.33, A = 1.78, B = 2.37, C = 3.16, D = 4.22, E = 5.62, F = 7.50, G = 0.0001,
H = 0.0003, I =0.001, J = 0.003, K = 0.01, L = 0.02, M = 0.05
c Sensor Response Time (s): (default is 0 = 0.00)
0 = 0.00, 1 = 0.02, 2 = 0.04, 3 = 0.06, 4 = 0.08, 5 = 0.10, 6 = 0.15, 7 = 0.20, 8 = 0.25,
9 = 0.30, A = 0.35, B = 0.4, C = 0.50, D = 0.60, E = 0.80, F = 1.00
d Setpoint Ramp Time (s): (default is 0 = 0.0)
0 = 0.0, 1 = 0.5, 2 = 1.0, 3 = 1.5, 4 = 2.0, 5 = 2.5, 6 = 3.0, 7 = 3.5, 8 = 4.0, 9 = 4.5,
A = 5.0, B = 5.5, C = 6.0, D = 6.5, E = 7.0, F = 7.5, G = 8.0, H = 8.5, I = 9.0, J =9.5,
K = 10.0
e, f, g, h are not used. Set 0000
Acknowledgement
command)
Remote
operation:
Note: Refer to chapter: «RS232
Command syntax» > «RS232
commands» > 'PID CONTROLLER
CONFIGURATION'.
289112EA