5700P Series Power Operator

Components

Circuit Breaker
On/Off Switch
Power Input
IEC C14 Appliance Inlet

General Information

UL labeled fire or smoke barrier door assemblies require that the 120VAC (60Hz) power input to the 5700P door
operator be supplied through normally closed alarm contacts of the alarm system / alarm panel.
120VAC power input to 5700P door operator to be through a NEMA 5-15 outlet located within 15 inches of Power
Input end of operator.
All wiring must conform to standard wiring practice in accordance with national and local wiring codes.
Unit is Non-Handed.
Door must swing freely through the entire opening and closing cycle before beginning the installation.
Use of an auxiliary door stop (by others) is always recommended.
An incorrectly installed or improperly adjusted door operator can cause property damage or personal injury. These
instructions should be followed to avoid the possibility of misapplication or misadjustment.

Technical Data

Input power:
120VAC, 60Hz
Power consumption:
.6 amps
Circuit breaker:
3 amps
Power supply:
24 V DC, max. 1.1 amp.
Door width:
28" - 48" Max. (71-122 cm)
Door weight:
100-250 lb Max. (43-113 kg)
Door opening angle:
up to 110° PULL side; up to 170° PUSH side;
Manually to 180° PUSH/PULL side
Hold open time:
5-30 seconds (A.D.A. 5 seconds min.)
Copyright © 2016, 2019-2020, ASSA ABLOY Accessories and Door Controls Group, Inc. All rights reserved. Reproduction in
whole or in part without the express written permission of ASSA ABLOY Accessories and Door Controls Group, Inc. is prohibited.
80-9357-0009-020 Rev 7 01/20
Motor Assembly
1600 Series
Closer Body
Pinion Extension/
Clutch Assembly
Accessory Terminal
(4-Position)
WARNING: Make sure (120V, 60Hz) input
power is turned OFF at facility's main circuit
breaker before proceeding with installation
Approved 2020-01-27
Inverter
Open/Close
Positioning
Magnets
Chain
Power Supply Cord
(125V/10A Rated 18AWG
18" Max, NEMA 5-15P
and IEC320-C13 Connectors.
Cord must be UL listed.)
Notes:
Conduit hole is for low voltage Class 2 wiring ONLY.
Input power is NOT to be hard wired into unit.
Power cord is to be routed so that it is NOT in any part
of a doorway, window opening, wall, ceiling or floor not
attached or otherwise secured to the building structure,
and not concealed behind walls.
Activation devices: push plates, access control, mats,
touchless wall switches, etc.
Maximum wire size is:
14AWG at terminals 1 - 4 on Accessory Terminal
Rate of operation shall not exceed 300 cycles of opening
and closing per hour.
Backplate
Reed Switch
3