5700 Series Power Operator
Components
Circuit Breaker
On/Off Switch
General Information
•
UL labeled fire or smoke barrier door assemblies require that the 120VAC (60Hz) power input to the 5700 door
operator be supplied through normally closed alarm contacts of the alarm system / alarm panel.
•
Power input to 5700 door operator must be 120VAC (60Hz) to terminals HOT and COM at terminal strip T1. Earth
ground (GND) to green screw on backplate.
•
All wiring must conform to standard wiring practice in accordance with national and local wiring codes.
•
Unit is Non-Handed.
•
Door must swing freely through the entire opening and closing cycle before beginning the installation.
•
Use of an auxiliary door stop (by others) is always recommended.
•
An incorrectly installed or improperly adjusted door operator can cause property damage or personal injury. These
instructions should be followed to avoid the possibility of misapplication or misadjustment.
Technical Data
Input power:
Power consumption:
Circuit breaker:
Power supply:
Door width:
Door weight:
Door opening angle:
Hold open time:
Copyright © 2016, 2019-2020, ASSA ABLOY Accessories and Door Controls Group, Inc. All rights reserved. Reproduction in
whole or in part without the express written permission of ASSA ABLOY Accessories and Door Controls Group, Inc. is prohibited.
80-9357-0008-020 Rev 6 01/20
1600 Series
Closer Body
T1 120VAC Power Input
Terminal (3-Position)
120VAC, 60Hz
.6 amps
3 amps
24 V DC, max. 1.1 amp.
28" - 48" Max. (71-122 cm)
100-250 lb Max. (43-113 kg)
up to 110° PULL side; up to 170° PUSH side;
Manually to 180° PUSH/PULL side
5-30 seconds (A.D.A. 5 seconds min.)
WARNING: Make sure (120V, 60Hz) input
power is turned OFF at facility's main circuit
breaker before proceeding with installation
Approved 2020-01-27
Motor Assembly
Chain
Pinion Extension/
Clutch Assembly
Accessory Terminal/
Activation Inputs
(4-Position)
Notes:
•
Permanent wiring is to be implemented as required by
local codes.
•
Activation devices: push plates, access control, mats,
touchless wall switches, etc.
•
Maximum wire size is:
12AWG at terminals HOT and COM (120VAC; 60Hz) on
T1 Power Input Terminal
14AWG at terminals 1 - 4 on Accessory Terminal
18AWG at terminals 22 - 25 on T1 Power Input Terminal
•
Rate of operation shall not exceed 300 cycles of opening
and closing per hour.
Inverter
Reed Switch
Open/Close
Positioning
Magnets
Backplate
3