Mircom TX3 Series Programming Manual page 28

Telephone access system
Table of Contents

Advertisement

2.7.21
Elevator Rest Timer
The "Elevator Restriction Timer" function lets you define the elevator access
time.
The elevator restriction cabinet houses up to 96 Form C type relay contacts.
These relay contacts are normally connected to the input circuits of the elevator
manufacturer's button controller. When a resident releases the door, a designated
relay is energized to signal the elevator button controller to enable a particular
floor select button on the elevator and disable all others.
The elevator is restricted to stop only on the selected floor. The time period for
these relays to remain in an energized state depends on the assigned timer period.
Note:
To set the Elevator Restriction Timer function
1.
2.
3.
4.
2.7.22
Speaker Volume
The "Speaker Volume" function lets you adjust the Entry Panel speaker volume.
To set the "Speaker Volume" function
1.
TX3 Telephone Access System Programming Manual
28
LT-979
Copyright 2018
Each elevator restriction cabinet can have only one common timer.
The timer range is 5 to 600 seconds, with 60 seconds as the default.
Press the arrow key to select the "Elevr Rest Tmr" and press the telephone
(enter) key. The "Elevr Rest Tmr" entry appears.
Elev Rest Timer
[ 060 ]
Press the up and down arrow keys to scroll through the numbers. The
range is 5 to 600 seconds and the default is 60 seconds.
Press the telephone (enter) key to accept the number in view.
Press info key to return to previous menu.
Press the arrow key to scroll to "Speaker volume" and press the telephone
(enter) key. The "Speaker volume" entry appears.
Speaker volume
[ 011 ]
Configuration
Version 2.7