E7 Return Air Temperature Thermistor Anomaly - Mitsubishi Electric FDF100VSXVD Technical Manual

Hide thumbs Also See for FDF100VSXVD:
Table of Contents

Advertisement

Error code
E7
Remote controller:
1. Applicable model
All models
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected by indoor return air
temperature thermistor (Thi-A)
3. Condition of Error displayed
• When the temperature thermistor
detects -50°C or lower for
5 seconds continuously, the
compressor stops. After 3-minute
delay, the compressor starts again
automatically, but if this error
occurs again within 60 minutes
after the initial detection.
4. Presumable cause
• Defective return air
temperature thermistor
connector
• Defective return air
temperature thermistor
• Faulty indoor control PCB
Note:
L E D
G r een
Red
Indoor
Stays OFF
Outdoor
5. Troubleshooting
Diagnosis
Is the
connection of return
air temperature thermistor
connector OK?
YES
Are the
characteristics of return air
temperature thermistor
OK?
Temperature-resistance characteristic
(Broken wire)
15 
10 
(Shot circuit)
-
166
Content
Return air temperature
thermistor anomaly
NO
NO
YES
°C
5k at 25
10 
20 
30 
40 
50 
Temperature (°C)
-
'11 • PAC-T-160
Countermeasure
Correct.
Connect
connector.
Defective return air
temperature thermistor
Replace.
Defective indoor control
PCB
Replace.
(Defective return air
temperature thermistor
input circuit)