3) Selection of installation location for the outdoor unit
Be sure to select a suitable installation place in consideration of following conditions.
〇 A place where it is horizontal, stable and can endure the unit weight and will not allow vibration transmittance of the unit.
〇 A place where it can be free from possibility of bothering neighbors due to noise or exhaust air from the unit
〇 A place where the unit is not exposed to oil splashes.
〇 A place where it can be free from danger of flammable gas leakage.
〇 A place where drain water can be disposed without any trouble.
〇 A place where the unit will not be affected by heat radiation from other heat source.
〇 A place where snow will not accumulate.
〇 A place where the unit can be kept away 5m or more from TV set and/or radio receiver in order to avoid any radio or TV interference.
〇 A place where good air circulation can be secured, and enough service space can be secured for maintenance and service of the unit safely.
〇 A place where the unit will not be affected by electromagnetic waves and/or high-harmonic waves generated by other equipment.
〇 A place where chemical substances like sulfuric gas, chloric gas, acid and alkali (including ammonia), which can harm the
unit, will not be generated and not remain.
〇 A place where strong wind will not blow against the outlet air blow of the unit.
4) Caution about selection of installation location
(1) If the unit is installed in the area where the snow will accumulate, following measures are required.
The bottom plate of unit and intake, outlet may be blocked by snow.
1. Install the unit on the base so
2. Provide a snow hood to
that the bottom is higher than
the outdoor unit on site.
snow cover surface.
Regarding outline of a snow
hood, refer to our technical
manual.
Since drain water generated by defrost control may freeze, following measures are required.
Don't execute drain piping work by using a drain elbow and drain grommets (optional parts). [Refer to Drain piping work.]
Recommend setting Defrost Control (SW3-1) and Snow Guard Fan Control (SW3-2). [Refer to Setting SW3-1, SW3-2.]
(2) If the unit can be affected by strong wind, following measures are required.
Strong wind can cause damage of fan (fan motor), or can cause performance degradation, or can trigger anomalous
stop of the unit due to rising of high pressure.
1.Install the outlet air blow side of the
2.Install the outlet air blow side of
unit to face a wall of building, or
the unit in a position perpendicular
provide a fence or a windbreak screen.
to the direction of wind.
Over 500 mm
Wind direction
2. REFRIGERANT PIPING WORK
1) Restrictions on unit installation and use
Check the following points in light of the indoor unit specifications and the installation site.
Observe the following restrictions on unit installation and use. Improper installation can result in a compressor failure or performance degradation.
One-way pipe length difference from the first branching point to the indoor unit
Descriptions
Model for outdoor units
100VN,125VN,100VS,125VS
140VN,140VS
One-way pipe length of
refrigerant piping
100VNX,125VNX,100VSX,125VSX
140VNX,140VSX
100VN,125VN,100VS,125VS
140VN,140VS
Main pipe length
100VNX,125VNX,100VSX,125VSX
140VNX,140VSX
One-way pipe length between the first
140VN,140VS,
branching point from to the second
140VNX,140VSX
branching point
One-way pipe length after the first
100VN,125VN,100VS,125VS,
branching point
100VNX,125VNX,100VSX,125VSX
One-way pipe length after the
first branching point and second
140VN,140VS,140VNX,140VSX
branching point
Twin type
One-way pipe length difference
from the first branching point to
140VN,140VS,
Triple type
the indoor unit
140VNX,140VSX
One-way pipe length difference
140VN,140VS,
from the second branching point
140VNX,140VSX
to the indoor unit
Elevation difference between
When the outdoor unit is positioned higher,
indoor and outdoor units
When the outdoor unit is positioned lower,
Elevation difference between indoor units
The use restrictions appearing in the table above are applicable to the standard pipe size combinations shown in the table below. Where an existing pipe system is
CAUTION
utilized, different one-way pipe length restrictions should apply depending on its pipe size. For more information, see " 6. UTILIZATION OF EXISTING PIPING."
With the triple pipe connection, the way of use is different when the difference of one-way pipe length after the first branching point is 3m to 10m. For details, refer
to the above table and right figure.
Note (1) Install the indoor units so that L + L1 becomes the longest one-way pipe.
Keep the pipe length difference between L1 and (La + L2) or (La + L3) within 10m.
2) Determination of pipe size
Determine refrigerant pipe size pursuant to the following guidelines based on the indoor unit specifications.
Outdoor unit connected
Refrigerant piping (branch pipeL)
Indoor unit connected
In the case of a single type
Capacity of indoor unit
Branching pipe set
Refrigerant piping (branch pipe L1,L2)
In the case of a twin type
Indoor unit connected
Capacity of indoor unit
Branching pipe set
Refrigerant piping (branch pipe L1,L2,L3)
In the case of a triple type A
Indoor unit connected
Capacity of indoor unit
Branching pipe set
Refrigerant piping (branch pipe La)
Refrigerant piping (branch pipe L1)
In the case of a triple type B
Indoor unit connected
Refrigerant piping (branch pipe L2,L3)
Indoor unit connected
Capacity of indoor unit
When the 50V or 60V model is connected as an indoor unit, always use a φ9.52 liquid pipe for the branch (branching pipe – indoor unit) and a different
CAUTION
diameter joint supplied with the branching pipe set for connection with the indoor unit (φ6.35 on the liquid pipe side).
If a φ6.35 pipe is used for connection with a branching pipe, a refrigerant distribution disorder may occur, causing one of the indoor units to fall short of
the rated capacity.
A riser pipe must be a part of the main. A branching pipe set should be installed horizontally at a point as close to an indoor unit as possible.
A branching part must be dressed with a heat-insulation material supplied as an accessory.
For the details of installation work required at and near a branching area, see the installation manual supplied with your branching pipe set.
About brazing
Brazing must be performed under a nitrogen gas flow.
Without nitrogen gas, a large quantity of foreign matters (oxidized film) are
created, causing a critical failure from capillary tube or expansion valve clogging.
3) Refrigerant pipe wall thickness and material
Select refrigerant pipes of the table shown on the right wall thickness and material as
specified for each pipe size.
This unit uses R410A. Always use 1/2H pipes having a 1.0mm or thicker wall for φ19.05
or larger pipes, because O-type pipes do not meet the pressure resistance requirement.
3. Install the unit under eaves
or providen the roof on site.
3.The unit should be installed on
the stable and level foundation.
If the foundation is not level,
tie down the unit with wires.
Wind direction
Marks appearting in the drawing
< 3m
Dimensional
Triple type A
Single type
Twin type
limitations
− 
≦ 50m
L+L1+L2+L3
L
L+L1+L2
− 
≦ 100m
L+L1+L2+L3
− 
≦ 50m
L
− 
L
− 
≦ 100m
L
≦ 5m
− 
− 
− 
− 
≦ 30m
− 
L1, L2
L1, L2, L3
≦ 27m
− 
− 
− 
− 
≦ 10m
|L1−L2|,|L2−L3|,|L3−L1|
≦ 3m
− 
|L1−L2| 
≦ 10m
− 
≦ 10m
− 
− 
− 
≦ 30m
H
H
H
≦ 15m
≦ 0.5m
− 
h
h1, h2, h3
Model 100V
Model 125V
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
φ15.88
φ9.52
φ15.88
φ9.52
φ15.88
Flare
Flare
Flare
Flare
Flare
φ15.88
φ9.52
φ15.88
φ15.88
φ9.52
φ9.52
φ9.52
φ15.88
φ15.88
φ15.88
Model 100V
Model 125V
DIS-WA1
DIS-WA1
φ9.52
φ9.52
φ12.7
φ12.7
φ15.88
φ6.35
φ6.35
φ12.7
φ12.7
φ15.88
Model 50V×2
Model 60V×2
φ12.7
− 
− 
φ12.7
φ15.88
φ12.7
− 
− 
φ12.7
φ12.7
Taping
Only use nitrogen gas (N
Pipe diameter
[mm]
Minimum pipe wall thickness
[mm]
Pipe material*
*Phosphorus deoxidized seamless copper pipe C1220T, JIS H3300
5) Installation space
Walls surrounding the unit in the four sides are not acceptable.
There must be a 1-meter or larger space in the above.
Where a danger of short-circuiting exists, install guide louvers.
When more than one unit are installed, provide sufficient intake space consciously so that short-circuiting may not occur.
Where piling snow can bury the outdoor unit, provide proper snow guards.
A barrier wall placed in front of the exhaust diffuser must not be higher than the unit.
Example installation
Ⅱ 
Ⅰ  
Size
Open
Open
L1
5
L2
300
L3
150
300
L4
5
5
6) Installation
①  Anchor bolt fixed position
②  Notabilia for installation
Intake
Outlet
190
580
200
Use a long block to extend the width.
In installing the unit, fix the unit's legs with bolts specified on the left.
The protrusion of an anchor bolt on the front side must be kept within 15 mm.
Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.
Refer to the left illustrations for information regarding concrete foundations.
Install the unit in a level area. (With a gradient of 5 mm or less.)
Improper installation can result in a compressor failure, broken piping within the unit and abnormal noise generation.
7) To run the unit for a cooling operation, when the outdoor temperature
is –5°C or lower.
When the outdoor air temperature is -5°C or lower, provide a snow hood to the outdoor unit on site.
So that strong wind will not blow against the outdoor heat exchanger directly. Regarding outline of a snow hood,
refer to our technical manual.
< Single type >
3m
Triple type B
− 
L+La+L1+L2+L3
− 
L+La+L1+L2+L3
− 
L
− 
L
< Twin type >
La
− 
L1 (1)
La+L2, La+L3
(1)
− 
L−(La+L2), L1−(La+L3)
(1)
|L2−L3| 
H
h1, h2, h3
< Triple type >
Type A
Model 140V
Liquid pipe
φ9.52
Flare
φ9.52
φ9.52
Model 140V
DIS-WA1
φ9.52
φ9.52
< Triple type >
Model 71V×2
DIS-TA1
Type B
φ9.52
φ6.35
Model 50Vx3
DIS-WA1
φ9.52
φ9.52
DIS-WA1
φ9.52
φ6.35
Model 50V×3
Plug the end of the pipe with tape, or other
<N
> 
material, and fill the pipe with nitrogen gas.
2
)
2
Brazing
6.35
9.52
12.7
15.88
22.22
0.8
0.8
0.8
1.0
1.0
O-type pipe
O-type pipe
O-type pipe
O-type pipe
1/2H-type pipe
-
-
73
73
-
-
'11 • PAC-T-160
(mm)  
L
Intake
3
L
Ⅲ 
2
500
L
4
Intake
Open
150
service
Outlet
(
)
space
L
1
5
Fasten with bolts
(M10-12)
Use a thicker block to anchor deeper.
Indoor unit
H
L
Outdoor unit
Indoor unit
(The unit of which elevation difference from the outdoor unit is the largest.)
Indoor unit
L1
H
L2
L (riser)
Outdoor unit
Indoor unit
(The unit of which elevation difference from the outdoor unit is the largest.)
Indoor unit
Indoor unit
L2
H
L1
L3
L (riser)
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
L2
H
L3
La
L1
L (riser)
Outdoor unit
Primary side
Secondary side
Station valve
0.5MPa
Hand
Nitrogen
Relief valve
gas
NOTE
25.4
28.58
1.0
1.0
Select pipes having a wall thickness larger
than the specified minimum pipe thickness.
1/2H-type pipe
1/2H-type pipe
h
h1
h3
h2
h1
h3
h2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents