Mitsubishi Electric Mr.SLIM PLA-RP·BA Technical Data Book

Mitsubishi Electric Mr.SLIM PLA-RP·BA Technical Data Book

Split-type, heat pump air conditioners

Advertisement

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
TECHNICAL DATA BOOK
PLA-RP·BA/BA2/BA3
<Indoor unit>
[Model names]
PEAD-RP·JA(L)
PEAD-RP·EA(2)
PEAD-RP·GA
PKA-RP·HAL
PKA-RP·KAL
PKA-RP·GAL
PKA-RP·FAL(2)
<Outdoor unit>
[Model names]
Zubadan
R410A
CONTENTS
1. REFERENCE SERVICE MANUAL ············································· 2
2. SPECIFICATIONS ······································································ 3
3. OUTLINES AND DIMENSIONS ··············································· 12
4. WIRING DIAGRAM ··································································· 24
5. REFRIGERANT SYSTEM DIAGRAM ······································ 36
6. PERFORMANCE CURVES ······················································ 38
7. CORRECTION FACTORS ························································ 40
9. AIR FLOW DATA ······································································ 44
10. NOISE CRITERION CURVES ·················································· 60
11. OPTIONAL PARTS ············································································74
March 2010
No. OCS11
REVISED EDITION-B
INVERTER
Revision :
• PLA-RP·BA3, PKA-RP·HAL/KAL
and PEAD-RP·JA(L) are added,
and the data of PUHZ-HRP·HA2
has been modified in REVISED
EDITION-B.
• Some descriptions have been
modified.
• Please void OCS11
REVISED EDITION-A.

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric Mr.SLIM PLA-RP·BA

  • Page 1: Table Of Contents

    SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS March 2010 No. OCS11 REVISED EDITION-B TECHNICAL DATA BOOK R410A INVERTER PLA-RP·BA/BA2/BA3 <Indoor unit> Revision : • PLA-RP·BA3, PKA-RP·HAL/KAL [Model names] PEAD-RP·JA(L) and PEAD-RP·JA(L) are added, and the data of PUHZ-HRP·HA2 has been modified in REVISED PEAD-RP·EA(2) EDITION-B.
  • Page 2: Puhz-Hrp71/100Vha

    REFERENCE SERVICE MANUAL For information on service, please refer to the service manual as follows. 1-1. INDOOR UNIT Model Name Service Ref. Service Manual No. PLA-RP35/50/60/100/125BA PLA-RP35/50/60/100/125BA#2.UK OCH412 PLA-RP71/100/125BA2 PLA-RP71/100/125BA2.UK OCB412 OCH459 PLA-RP100BA3 PLA-RP100BA3 OCB459 OCH453 PKA-RP35/50HAL PKA-RP35/50HAL OCB453 OCH452 PKA-RP60/100KAL PKA-RP60/100KAL.TH OCB452...
  • Page 3: Specifications

    SPECIFICATIONS 2-1. CEILING CASSETTE TYPE PLA-RP100BA3 Model name Indoor unit PLA-RP71BA2 PLA-RP100BA2 Outdoor unit PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100VHA2 34,100 Cooling Capacity Btu/h 24,200 34,100 7.1 ( 4.9 - 8.1 ) 10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 ) 2.44 Total input 1.94...
  • Page 4 PLA-RP100BA3 Model name Indoor unit PLA-RP100BA2 PLA-RP125BA2 PUHZ-HRP100YHA2 Outdoor unit PUHZ-HRP100YHA2 PUHZ-HRP125YHA2 34,100 34,100 42,700 Cooling Capacity Btu/h 10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 ) 12.5 ( 5.5 - 14.0 ) 2.50 2.50 3.79 Total input 4.00 4.00 3.30...
  • Page 5 Model name Indoor unit PLA-RP100BA PLA-RP100BA PLA-RP125BA Outdoor unit PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA Cooling Capacity Btu/h 34,100 34,100 42,700 10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 ) 12.5 ( 5.5 - 14.0 ) Total input 3.02 3.02 3.87 3.31 3.31...
  • Page 6 2-2. CEILING-CONCEALED TYPE Model Name Indoor Unit PEAD-RP71JA(L) PEAD-RP100JA(L) PEAD-RP100JA(L) PEAD-RP125JA(L) Outdoor Unit PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2 Cooling Capacity Btu/h 24,200 34, 100 34, 100 42,700 7.1 (3.3 - 8.1) 10.0 (4.9 - 11.4) 10.0 (4.9 - 11.4) 12.5 (5.5 - 14.0) Total Input 2.15 (2.13) 3.06 (3.04)
  • Page 7 Model name Indoor unit PEAD-RP71EA PEAD-RP100EA2 PUHZ-HRP71VHA PUHZ-HRP100VHA Outdoor unit PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 24,200 34,100 Cooling Capacity Btu/h 7.1 (4.9 - 8.1 ) 10.0 ( 4.9 - 11.4 ) Total input 2.15 3.06 3.30 3.27 Energy label class 0.83 0.86 Heating Capacity Btu/h 27,300...
  • Page 8 Model name Indoor unit PEAD-RP100EA2 PEAD-RP125EA PUHZ-HRP100YHA PUHZ-HRP125YHA Outdoor unit PUHZ-HRP100YHA2 PUHZ-HRP125YHA2 34,100 42,700 Cooling Capacity Btu/h 10.0 ( 4.9 - 11.4 ) 12.5 ( 5.5 - 14.0 ) 3.06 3.89 Total input 3.27 3.21 Energy label class 0.86 0.82 38,200 47,800 Heating...
  • Page 9 Model name Indoor unit PEAD-RP71GA PEAD-RP100GA PEAD-RP100GA PUHZ-HRP71VHA PUHZ-HRP100VHA PUHZ-HRP100YHA Outdoor unit PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 Cooling Capacity Btu/h 24,200 34,100 34,100 7.1 ( 4.9 - 8.1 ) 10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 ) Total input 2.15 3.08 3.08...
  • Page 10 2-3. WALL-MOUNTED TYPE Model Name Indoor Unit PKA-RP100KAL PKA-RP100KAL Outdoor Unit PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 Cooling Capacity Btu/h 34,100 10.0 (4.9 - 11.4) Total Input 2.93 3.41 Energy label class 0.73 Heating Capacity Btu/h 38,200 11.2 (4.5 - 14.0) Total Input 3.10 3.61 Energy label class Booster heater...
  • Page 11 Model name Indoor unit PKA-RP100FAL PKA-RP100FAL PUHZ-HRP100VHA PUHZ-HRP100YHA Outdoor unit PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 34,100 34,100 Cooling Capacity Btu/h 10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 ) Total input 2.93 2.93 3.41 3.41 Energy label class 0.77 0.77 38,200 38,200 Heating...
  • Page 12: Outlines And Dimensions

    OUTLINES AND DIMENSIONS INDOOR UNIT PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA PLA-RP100BA PLA-RP125BA PLA-RP71BA2 PLA-RP100BA2 PLA-RP100BA3 PLA-RP125BA2 Unit : mm Ceiling hole 20~45 860~910 20~45 Detail connecting of Branch duct(Both aspects) Fresh air Suspension bolt pitch intake hole Cut out hole Remote controller terminal block Indoor unit/Outdoor unit Branch duct hole...
  • Page 13 PEAD-RP35, 50, 60, 71, 100, 125JA Unit : mm 2xE- 2.9 Suspension bolt hole 4-14x30 Slot outlet inlet Air Filter 643 (Suspension bolt pitch) Terminal block Less than 300mm (Remote controller transmission line) Refrigerant piping Flare connection (liquid) 175±5mm Drain pipe Drain pump (Actual length) (O.D.
  • Page 14 PEAD-RP35, 50, 60, 71, 100, 125JAL Unit : mm 2xE- 2.9 Suspension bolt hole 4-14x30 Slot outlet inlet Air Filter 643 (Suspension bolt pitch) Terminal block (Remote controller transmission line) Refrigerant piping 175±5mm Flare connection (liquid) (Actual length) Control box 2×2- 2.9 Drain hose (I.D.
  • Page 15 PEAD-RP35EA2 Unit : mm PEAD-RP50EA PEAD-RP60EA Model R410A Outdoor unit : 6.35 R410A Outdoor unit : 12.7 RP35,50 R407C Outdoor unit : 9.52 R407C Outdoor unit : 15.88 Outdoor unit (SUZ) : 6.35 15.88 RP60 1012 1070 1044 R407C Outdoor unit : 9.52 Initial setting Service space:500 or more 10- 3 (RP35,50)
  • Page 16 Unit : mm PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA Model Outdoor unit(SUZ) : 6.35 15.88 RP60 1125 1090 1050 1012 Other outdoor unit : 9.52 * 1050 RP71 1125 1090 1012 9.52 15.88 R410A Outdoor unit : 15.88 * RP100 1365 1330 1290 1252 1080 9.52...
  • Page 17 PKA-RP35HAL PKA-RP50HAL Unit : mm Top side Mount board Front side Right side Left side Knockout hole Knockout hole for left piping for right piping Front side (Grille open) Sleeve Through hole (purchased locally) Terminal block for outdoor unit 65~ 80 65~ 80 Terminal block for power supply (option) Terminal block for...
  • Page 18 PKA-RP60KAL PKA-RP100KAL Unit : mm Top side 423.7 431.7 Right side Left side Front side Mount board Knockout hole for left piping (855) Operation lamp 1170 Knockout hole for DEFROST/STAND BY lamp right piping Receiver Front side (Grille open) Terminal block for outdoor unit Terminal block for power supply (option) Terminal block for MA-remote controller (option)
  • Page 19 PKA-RP35GAL PKA-RP50GAL Unit : mm...
  • Page 20 PKA-RP50FAL2 Unit : mm PKA-RP60FAL Display section Emergency switch(Heat) Receiving Emergency switch(Cool) section Defrosting Initial heating lamp Power lamp Front Right side 1400 Left side Knockout hole for right piping 1090 Air intake Refrigerant pipe. Drain pipe Terminal block for indoor/outdoor connecting line Liquid pipe Knockout hole for Terminal block for heater (PKH only)
  • Page 21 PKA-RP100FAL Unit : mm Display section Emergency switch(Heat) Emergency switch(Cool) Receiving section Defrosting Initial heating lamp Power lamp Front Knockout hole for right piping Right side Left side 1680 1370 Air intake Knockout hole for left piping Terminal block for indoor/outdoor connecting line Liquid pipe Terminal block for heater (PKH only) Gas pipe...
  • Page 22 OUTDOOR UNIT Unit : mm PUHZ-HRP71VHA PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA...
  • Page 23 Unit : mm PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2...
  • Page 24: Wiring Diagram

    WIRING DIAGRAM 4-1. INDOOR UNIT PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA PLA-RP100BA PLA-RP125BA PLA-RP71BA2 PLA-RP100BA2 PLA-RP100BA3 PLA-RP125BA2 <Table 1> SW1 (MODEL SELECTION) [LEGEND] MODELS SETTING SYMBOL NAME SYMBOL NAME 1 2 3 4 5 PLA-RP·BA INDOOR CONTROLLER BOARD FAN MOTOR CN2L VANE MOTOR CONNECTOR (LOSSNAY) 1 2 3 4 5 PLA-RP71/100/125BA2...
  • Page 25 PEAD-RP35JA(L) PEAD-RP50JA(L) PEAD-RP60JA(L) PEAD-RP71JA(L) PEAD-RP100JA(L) PEAD-RP125JA(L)
  • Page 26 PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA PEAD-RP100EA2 PEAD-RP125EA [LEGEND] NAME NAME NAME SYMBOL SYMBOL SYMBOL I.B. INDOOR CONTROLLER BOARD SWITCH(CAPACITY CODE) TERMINAL BLOCK FUSE FUSE(T6.3AL250V) SWITCH(EMERGENCY OPERATION) (INDOOR/OUTDOOR CONNECTING LINE) VARISTOR RELAY(DRAIN PUMP) TERMINAL BLOCK(REMOTE CONTROLLER) CN2L CONNECTOR(LOSSNAY) RELAY(FAN MOTOR) INTAKE AIR TEMP. THERMISTOR /15kΩ, 25 /5.4kΩ...
  • Page 27 PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA [LEGEND] SYMBOL NAME SYMBOL NAME SYMBOL NAME I.B. INDOOR CONTROLLER BOARD SWITCH(MODEL SELECTION) TERMINAL BLOCK(REMOTE CONTROLLER) FUSE FUSE(T6.3AL250V) SWITCH(CAPACITY CODE) INTAKE AIR TEMP.THERMISTOR SWITCH(EMERGENCY OPERATION) , 25 /5.4 DETECT) VARISTOR kΩ kΩ CN2L CONNECTOR(LOSSNAY) RELAY(DRAIN PUMP) PIPE TEMP. THERMISTOR/LIQUID , 25 /5.4 DETECT) CN24 CONNECTOR(HEATER)
  • Page 28: Model Selection

    PKA-RP35HAL PKA-RP50HAL [Explanation of symbols] Symbol Name Symbol Name Indoor controller board Vane motor CN2L Connector (LOSSNAY) Fan motor CN32 Connector ( Remote switch) Switch board CN41 Connector (HA terminal-A) SWE2 Emergency operation CN51 Connector (Centrally control) Terminal block(Indoor unit Power (option)) CN90 Connector (Remote operation adapter) Terminal block (Indoor/outdoor connecting line)
  • Page 29 PKA-RP60KAL PKA-RP100KAL [LEGEND] SYMBOL NAME SYMBOL NAME Indoor controller board Vane motor CN2L Connector (LOSSNAY) Fan motor CN32 Connector (Remote switch) Switch board CN41 Connector (HA terminal-A) SWE2 Emergency operation CN51 Connector (Centrally control) Terminal block (Indoor unit Power (option)) CN90 Connector (Remote operation adapter) Terminal block (Indoor/outdoor connecting line)
  • Page 30 PKA-RP35GAL PKA-RP50GAL [LEGEND] SYMBOL NAME SYMBOL NAME SYMBOL NAME INDOOR POWER BOARD CAPACITOR <FAN MOTOR> WIRELESS REMOTE CONTROLLER BOARD INDOOR CONTROLLER BOARD FAN MOTOR RECEIVING UNIT FUSE FUSE (T6.3AL250V) VANE MOTOR BUZZER VARISTOR TERMINAL BLOCK (HEATER) PKH-P.GALH LED1 LED <RUN INDICATOR> models only or option for PKA-RP.GAL models.
  • Page 31 PKA-RP50FAL2 PKA-RP60FAL PKA-RP100FAL [LEGEND] SYMBOL NAME SYMBOL NAME SYMBOL NAME INDOOR POWER BOARD CAPACITOR(FAN MOTOR) WIRELESS REMOTE CONTROLLER BOARD INDOOR CONTROLLER BOARD FAN MOTOR RECEIVING UNIT FUSE FUSE(T6.3AL250V) VANE MOTOR BUZZER VARISTOR TERMINAL BLOCK (HEATER) PKH-P.FALH LED1 LED(RUN INDICATOR ) models only or option for PKA-RP.FAL models.
  • Page 32 4-2. OUTDOOR UNIT PUHZ-HRP71VHA PUHZ-HRP100VHA [LEGEND] SYMBOL NAME SYMBOL NAME SYMBOL NAME Terminal Block<Power Supply, Indoor/Outdoor> P.B. Switch<Model Select> Power Circuit Board Motor for Compressor Connection Terminal<U/V/W-Phase> Switch<Function Setup> TABU/V/W MF1, MF2 Fan Motor Switch<Function Setup> TABS/T Connection Terminal <L/N-Phase> 21S4 Solenoid Valve (Four-Way Valve) TABP1/P2/P...
  • Page 33 PUHZ-HRP100YHA PUHZ-HRP125YHA [LEGEND] SYMBOL NAME SYMBOL NAME SYMBOL NAME Terminal Block<Power Supply> P.B. Power Circuit Board Controller Circuit Board C.B. Terminal Block<Indoor/Outdoor > TB-U/V/W Connection Terminal<U/V/W-Phase> Switch<Forced Defrost, Defect History Record Motor for Compressor TB-L1/L2/L3 Reset, Refrigerant Adress> Connection Terminal<L1/L2/L3-Power Supply> MF1, MF2 Fan Motor TB-P2...
  • Page 34 PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 [LEGEND] SYMBOL NAME SYMBOL NAME SYMBOL NAME Terminal Block<Power Supply, Indoor/Outdoor> P.B. CN31 Connector<Emergency Operation> Power Circuit Board Motor for Compressor < > U/V/W Connection Terminal<U/V/W-Phase> Connector Connection for Option MF1, MF2 Fan Motor Connection Terminal <L-Phase> Connector<Connection for Option> 21S4 Solenoid Valve (Four-Way Valve) Connector<A-Control Service Inspection Kit>...
  • Page 35 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2 [LEGEND] SYMBOL NAME SYMBOL NAME SYMBOL NAME Terminal Block<Power Supply> P.B. Power Circuit Board C.B. Controller Circuit Board Terminal Block<Indoor/Outdoor > TB-U/V/W Connection Terminal<U/V/W-Phase> Switch<Manual Defrost, Defect History Record Motor for Compressor TB-L1/L2/L3 Connection Terminal<L1/L2/L3-Power Supply> Reset, Refrigerant Address> MF1, MF2 Fan Motor TB-P2...
  • Page 36: Refrigerant System Diagram

    REFRIGERANT SYSTEM DIAGRAM 5-1. INDOOR UNIT unit : mm PLA-RP·BA/BA2/BA3 PKA-RP·GAL PKA-RP·FAL(2) PEAD-RP·JA(L) PEAD-RP·EA(2) PEAD-RP·GA Strainer(#50) Heat exchanger Refrigerant GAS pipe connection (Flare) Thermistor TH5 (Cond./Eva. temperature) Refrigerant flow in cooling Refrigerant flow in heating Refrigerant LIQUID pipe connection (Flare) Distributor Thermistor TH2 with strainer(#50)
  • Page 37 Unit : mm (inch) 5-2. OUTDOOR UNIT PUHZ-HRP71VHA PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA Thermistor TH7 (Outdoor) Heat exchanger Thermistor Solenoid valve Ball valve (Outdoor (Four-way valve) 2-phase pipe) Refrigerant GAS pipe Strainer connection Charge plug (5/8 inch) Thermistor TH3 (High pressure) (Outdoor pipe) Charge plug Muffler High pressure...
  • Page 38: Performance Curves

    PERFORMANCE CURVES FOR THE COMBINATION OF OUTDOOR UNIT PUHZ-HRP·VHA(2), PUHZ-HRP·YHA(2) Rated cooling capacity Indoor intake air wet-bulb temperature <W.B. :> Outdoor intake air dry-bulb temperature <D.B. > Rated cooling input Indoor intake air wet-bulb temperature <W.B. :> Outdoor intake air dry-bulb temperature <D.B. >...
  • Page 39 Rated heating capacity Indoor intake air dry-bulb temperature <: D.B.> Outdoor ambient temp.(˚CWB) Rated heating input Indoor intake air dry-bulb temperature <: D.B.> Outdoor ambient temep.(ºCWB)
  • Page 40: Correction Factors

    CORRECTION FACTORS PUHZ-HRP71, 100VHA(2) PUHZ-HRP100, 125YHA(2) Cooling capacity correction factors Refrigerant piping length (one way) Outdoor unit PUHZ-HRP71VHA(2) 1.00 0.988 0.966 0.946 0.929 0.913 0.905 0.897 0.876 0.870 PUHZ-HRP100VHA(2) 1.00 0.985 0.957 0.931 0.908 0.886 0.876 0.865 0.846 0.829 PUHZ-HRP100YHA(2) PUHZ-HRP125YHA(2) 1.00 0.981...
  • Page 41: Applicable Extension Pipe For Each Model

    APPLICABLE EXTENSION PIPE FOR EACH MODEL 8-1. PIPE LENGTH 8-1-1. 1:1 SYSTEM Pipe length <Table 1> Maximum pipe length 9.52 12.7 Liquid <Marks in the table> pipe Thickness t0.8 t0.8 (mm) 12.7 15.88 19.05 15.88 19.05 pipe : It can be used. Thickness t0.8 t1.0...
  • Page 42 8-2. ADJUSTING THE AMOUNT OF REFRIGERANT • Check additional refrigerant charging amount referring to table 5, 6 when liquid pipe is one size larger than standard diameter. <Table 5> Required additional charge when the liquid pipe is one size larger than the standard diameter (1:1 SYSTEM) Refrigerant amount to be added (Exceeding 20m) Outdoor unit Liquid pipe O.D.
  • Page 43 8-3. CAPACITY CORRECTION CURVES Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered com- paring to the standard diameter.
  • Page 44: Air Flow Data

    AIR FLOW DATA 9-1. OUTLET AIR SPEED AND COVERAGE RANGE PLA-RP100BA PLA-RP125BA PLA-RP36BA PLA-RP50BA PLA-RP60BA PLA-RP71BA2 PLA-RP100BA2 PLA-RP125BA2 PLA-RP100BA3 Air fl ow /min. Air speed m/sec. Coverage range PKA-RP35GAL PKA-RP50GAL Air fl ow /min. Air speed m/sec. Coverage range m (ft) 10 (32.8) 10(32.8) PKA-RP50FAL2...
  • Page 45 9-2. PLA-RP·BA/BA2/BA3 9-2-1 FRESH AIR INTAKE AND BRANCH DUCT 1. Branch duct hole and fresh air intake hole (Fig. 1) At the time of i nstallation, use the duct holes ( cut out) located at the positions shown in Fig.1, as and when required. •...
  • Page 46 3. Fresh air intake volume & static pressure characteristics PLA-RP35~60BA PLA-RP71BA2 At using multi-function casement, standard filter 2 - inlet -100 -150 1 - inlet -200 Air flow rate [m /min] Direct intake to unit At using multi-function casement, high efficiency filter 2 - inlet -100 -100...
  • Page 47 4. Change of outlet numbers Indoor unit The optional air outlet is necessary. To change the air outlet number to 3-, or 2-way outlet, the outlet number should be closed with the operational air outlet shutter. When the air outlets are closed, close the vane by removing the vane connector.
  • Page 48 PLA-RP71BA2 4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct Duct Duct High High Airflow rate [m /min] Airflow rate [m /min] 3-way airflow (horizontal vane) Round duct 3-way airflow (horizontal vane) Rectangular duct Duct Duct Close Close High High...
  • Page 49 PLA-RP125BA(2) 4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct Duct Duct High High Airflow rate [m ³ /min] Airflow rate [m ³ /min] 3-way airflow (horizontal vane) Round duct 3-way airflow (horizontal vane) Rectangular duct Duct Duct Close Close...
  • Page 50 9-3. PEAD-RP·JA(L) Fan performance PEAD-RP35JA(L) PEAD-RP35JA(L) (External static pressure 100Pa) 220-240V 50Hz (External static pressure 35Pa) 220-240V 50Hz Rated point Limit Limit High Rated point Middle High Middle Airflow rate(m /min) Airflow rate(m /min) PEAD-RP35JA(L) PEAD-RP35JA(L) (External static pressure 50Pa) 220-240V 50Hz (External static pressure 150Pa) 220-240V 50Hz Rated point Limit...
  • Page 51 PEAD-RP50JA(L) PEAD-RP50JA(L) (External static pressure 35Pa) 220-240V 50Hz (External static pressure 100Pa) 220-240V 50Hz Limit Rated point Limit High High Rated point Middle Middle Airflow rate(m /min) Airflow rate(m /min) PEAD-RP50JA(L) PEAD-RP50JA(L) (External static pressure 50Pa) 220-240V 50Hz (External static pressure 150Pa) 220-240V 50Hz Rated point Limit High...
  • Page 52 PEAD-RP60JA(L) PEAD-RP60JA(L) (External static pressure 35Pa) 220-240V 50Hz (External static pressure 100Pa) 220-240V 50Hz Rated point Limit Limit High Rated point Middle High Middle Airflow rate(m /min) Airflow rate(m /min) PEAD-RP60JA(L) PEAD-RP60JA(L) (External static pressure 50Pa) 220-240V 50Hz (External static pressure 150Pa) 220-240V 50Hz Rated point Limit High...
  • Page 53 PEAD-RP71JA(L) PEAD-RP71JA(L) (External static pressure 35Pa) 220-240V 50Hz (External static pressure 100Pa) 220-240V 50Hz High Rated point Limit Limit Middle High Rated point Middle Airflow rate(m /min) Airflow rate(m /min) PEAD-RP71JA(L) PEAD-RP71JA(L) (External static pressure 50Pa) 220-240V 50Hz (External static pressure 150Pa) 220-240V 50Hz High Rated point Limit...
  • Page 54 PEAD-RP100JA(L) PEAD-RP100JA(L) (External static pressure 35Pa) 220-240V 50Hz (External static pressure 100Pa) 220-240V 50Hz Limit High Limit Rated point Middle Rated point High Middle Airflow rate(m /min) Airflow rate(m /min) PEAD-RP100JA(L) PEAD-RP100JA(L) (External static pressure 50Pa) 220-240V 50Hz (External static pressure 150Pa) 220-240V 50Hz High Rated point Limit...
  • Page 55 PEAD-RP125JA(L) PEAD-RP125JA(L) (External static pressure 35Pa) 220-240V 50Hz (External static pressure 100Pa) 220-240V 50Hz Limit High Limit High Middle Middle Rated point Rated point Airflow rate(m /min) Airflow rate(m /min) PEAD-RP125JA(L) PEAD-RP125JA(L) (External static pressure 50Pa) 220-240V 50Hz (External static pressure 150Pa) 220-240V 50Hz High High Limit...
  • Page 56 9-4. PEAD-RP·EA,EA2,GA 9-4-1. FAN PERFORMANCE AND CORRECTED AIR FLOW PEAD-RP35EA2 Fan Performance <30Pa> PEAD-RP50EA Capacity Corrected Airflow input Cooling 12 14 16 Airflow (CMM) 10 12 14 16 18 20 Airflow (CMM) Fan Performance <70Pa> Heating 12 14 16 Airflow (CMM) 10 12 14 16 18 20 22 Airflow (CMM) PEAD-RP60EA...
  • Page 57 PEAD-RP71EA Fan performance <70Pa> Fan performance <130Pa> Recommended range Recommended range 12 16 20 24 28 32 12 16 20 24 28 32 A i r f l o w ( C M M ) A i r f l o w ( C M M ) Corrected Airflow Heating Capacity...
  • Page 58 PEAD-RP60GA PEAD-RP71GA...
  • Page 59 PEAD-RP100GA...
  • Page 60: Noise Criterion Curves

    NOISE CRITERION CURVES 10-1. INDOOR UNIT PLA-RP35BA PLA-RP50BA NOTCH SPL(dB) LINE NOTCH SPL(dB) LINE High High Medium1 Medium1 Medium2 Medium2 NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 APPROXIMATE APPROXIMATE THRESHOLD OF THRESHOLD OF HEARING FOR HEARING FOR NC-20 NC-20 CONTINUOUS...
  • Page 61 PLA-RP100BA PLA-RP125BA NOTCH SPL(dB) LINE NOTCH SPL(dB) LINE High High PLA-RP100BA2 PLA-RP125BA2 Medium1 Medium1 PLA-RP100BA3 Medium2 Medium2 NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 APPROXIMATE APPROXIMATE THRESHOLD OF THRESHOLD OF HEARING FOR HEARING FOR NC-20 NC-20 CONTINUOUS CONTINUOUS NOISE NOISE...
  • Page 62 PEAD-RP·JA(L) Ceiling concealed Aux.duct Measurement location Noise level at anechoic room (Low-Middle-High) Unit: dB(A) Exrernal static pressure Model 35Pa 50Pa 70Pa 100Pa 150Pa PEAD-RP35JA(L) 23-26-29 23-27-30 24-28-31 26-29-33 29-33-37 PEAD-RP50JA(L) 25-30-34 26-31-35 28-32-36 29-33-37 31-35-39 PEAD-RP60JA(L) 25-28-32 25-29-33 26-30-34 27-31-35 29-34-38 PEAD-RP71JA(L) 25-29-34...
  • Page 63 PEAD-RP35JA(L) High High External static pressure 35Pa External static pressure 100Pa Middle Middle NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 Approximate Approximate minimum audible minimum audible NC-20 NC-20 limit on continuous limit on continuous noise noise 1000 2000 4000 8000...
  • Page 64 PEAD-RP50JA(L) High High External static pressure 35Pa External static pressure 100Pa Middle Middle NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 Approximate Approximate minimum audible minimum audible NC-20 NC-20 limit on continuous limit on continuous noise noise 1000 2000 4000 8000...
  • Page 65 PEAD-RP60JA(L) High High External static pressure 35Pa External static pressure 100Pa Middle Middle NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 Approximate Approximate minimum audible minimum audible NC-20 NC-20 limit on continuous limit on continuous noise noise 1000 2000 4000 8000...
  • Page 66 PEAD-RP71JA(L) High High External static pressure 35Pa External static pressure 100Pa Middle Middle NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 Approximate Approximate minimum audible minimum audible NC-20 NC-20 limit on continuous limit on continuous noise noise 1000 2000 4000 8000...
  • Page 67 PEAD-RP100JA(L) High High External static pressure 35Pa External static pressure 100Pa Middle Middle NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 Approximate Approximate minimum audible minimum audible NC-20 NC-20 limit on continuous limit on continuous noise noise 1000 2000 4000 8000...
  • Page 68 PEAD-RP125JA(L) High High External static pressure 35Pa External static pressure 100Pa Middle Middle NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 Approximate Approximate minimum audible minimum audible NC-20 NC-20 limit on continuous limit on continuous noise noise 1000 2000 4000 8000...
  • Page 69 PEAD-RP35EA2 (External static PEAD-RP35EA2 (External static pressure 30Pa) pressure 70Pa) PEAD-RP50EA PEAD-RP50EA High High NC60 NC60 NC50 NC50 NC40 NC40 NC30 NC30 NC20 NC20 Approximate minimum Approximate minimum audible limit on audible limit on continuous noise continuous noise 1000 2000 4000 8000 1000...
  • Page 71 SOUND LEVELS Low-Middle-High Model Sound level dB (A) PKA-RP35, 50HAL 36 - 40 - 43 PKA-RP60KAL 39 - 42 - 45 PKA-RP100KAL 41 - 45 - 49 PKA-RP35HAL PKA-RP60KAL PKA-RP50HAL External static pressure : 0Pa External static pressure : 0Pa Power source : 220, 230, 240V, 50Hz Power source : 220, 230, 240V, 50Hz 70.0...
  • Page 72 PKA-RP35GAL PKA-RP50FAL2 SPL(dB) LINE NOTCH NOTCH SPL(dB) LINE High High PKA-RP50GAL PKA-RP60FAL Medium1 Medium2 NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 APPROXIMATE APPROXIMATE THRESHOLD OF THRESHOLD OF HEARING FOR HEARING FOR NC-20 NC-20 CONTINUOUS CONTINUOUS NOISE NOISE 1000 2000 4000...
  • Page 73 10-2. OUTDOOR UNIT SPL(dB) SPL(dB) PUHZ-HRP71VHA MODE LINE PUHZ-HRP71VHA2 MODE LINE COOLING COOLING PUHZ-HRP100VHA PUHZ-HRP100VHA2 HEATING HEATING PUHZ-HRP100YHA PUHZ-HRP100YHA2 PUHZ-HRP125YHA PUHZ-HRP125YHA2 NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 APPROXIMATE APPROXIMATE THRESHOLD OF THRESHOLD OF HEARING FOR HEARING FOR NC-20 NC-20 CONTINUOUS...
  • Page 74: Optional Parts

    OPTIONAL PARTS 11-1. INDOOR UNIT Part Name Model Name Applicable model Remote sensor PAC-SE41TS-E PAC-SF40RM-E ( 1) Remote operation adapter Multiple remote controller adapter PAC-SA88HA-E (1 pc.) All models PAC-725AD (10 pcs.) Remote on/off adapter PAC-SE55RA-E PEAD-RP•EA(2) Power supply terminal kit L/N/Earth PAC-SG96HR-E PKA-RP•GAL/FAL(2)
  • Page 75 11-2. OUTDOOR UNIT Applicable model Part Name Model Name M-NET adapter PAC-SF81MA-E PUHZ-HRP71-125 PUHZ-HRP71-125 A-control service tool PAC-SK52ST PUHZ-HRP71-125 Drain socket PAC-SG61DS-E PUHZ-HRP71-125 Air outlet guide (HRP71/100/125 needs 2 pieces.) PAC-SG59SG-E PUHZ-HRP71-125 Air protect guide (HRP71/100/125 needs 2 pieces.) PAC-SH63AG-E PUHZ-HRP71-125 Drain pan PAC-SG64DP-E...
  • Page 76 HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Copyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Mar. 2010 No.OCS11 REVISED EDITION-B PDF 4 Distributed in Sep. 2008 No.OCS11 REVISED EDITION-A PDF 6 Distributed in Oct. 2007 No.OCS11 PDF 7 New publication, effective Mar.