Mitsubishi Electric FDF100VSXVD Technical Manual page 160

Hide thumbs Also See for FDF100VSXVD:
Table of Contents

Advertisement

Error code
WAIT
Remote controller:
1. Applicable model
All models
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Faulty indoor control or
power PCB
• Defective remote controller
• Broken remote controller wire
• Faulty outdoor control PCB
• Broken connection wires
Note:
L E D
G r een
Red
Stays OFF
Indoor
Outdoor
5. Troubleshooting
Diagnosis
WAIT
"
" is still displayed on the
remote controller LED 2 minutes
after power ON.
YES
Is the outdoor
unit control green LED
flashing?
YES
Is the indoor
unit green LED flashing?
YES
Is the outdoor unit
control red LED flashing
twice?
YES
Are wires
connected properly between indoor/
outdoor units?
YES
Is approx.
DC20V detected between - on
the outdoor unit terminal
block?
YES
Is approx.
DC20V detected between - on
the indoor unit terminal
block?
-
159
Content
Communication error at
initial operation (1/3)
To next page.
NO
NO
NO
NO
NO
NO
YES
-
'11 • PAC-T-160
Countermeasure
A
Defective indoor control
PCB Replace.
Defective indoor control PCB
Replace.
Defective remote controller Replace.
Broken remote controller wire Y
Replace.
Correct connection wires
between indoor and
outdoor units.
Defective outdoor control
PCB Replace.
Defective connection wire
(Broken)
Noise
Defective indoor control or
power PCB Replace.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents