Current Cut - Mitsubishi Electric FDF100VSXVD Technical Manual

Hide thumbs Also See for FDF100VSXVD:
Table of Contents

Advertisement

Error code
Indoor control PCB
E42
Remote controller:
Outdoor control PCB
1. Applicable model
All models
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
compressor stopping.
3. Condition of Error displayed
• If the output current of inveter
it makes the compressor
stopping.
• After 3-minute delay, the
compressor restarts, but if this
amonaly occurs 4 times within
30 minute after the intial
detection. (Model FDC71 –
250 only)
4. Presumable cause
• The valves closed
• Faulty power supply
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module
Note:
LED
Green
Keeps flashing
Keeps flashing
Outdoor
Yellow LED or Red LED Green LED
inverter
1 time flash or 5 times flash
PCB
5. Troubleshooting
Is the
Power supply
voltage OK?
YES
Are the
service valves
opened?
YES
Is the
high pressure
during operation
OK?
YES
Is the
checked result of
insulation resistance and
coil resistance (1) of
compressor motor
OK?
YES
To next page.
Red
Content
Stays OFF
1 time flash

Current cut (1/2)

Keeps flashing
Diagnosis
NO
NO
NO
NO
(1) 1.154 or more at 20°C (Model FDC71)
0.293 or more at 20°C (Models FDC100〜140)
1.172 or more at 20°C (Models FDC100〜140)
0.334 or more at 20°C (Models FDC200, 250)
182
'11 • PAC-T-160
Countermeasure
Check power supply.
Open the valves.
Check refrigerant amount
and refregerant circuit
*In case of transitional
increase of high pressure
and/or test run, several
times restarting may
recover it, because liquid
refrigerant (migrated)
in the compresser is
discharged from the
compressor.
Replace compressor.